The Critical Component
EN Series User Manual
29
4. Press Enter.
Setting All Outlet Default States Upon Startup of EN2000 and EN6000 Series PDUs
The EN2000 and EN6000 Series PDUs allow the user to determine the initial power status of the entire bank of
outlets upon PDU power up.
1. Select the PDU folder from the PDU Explorer.
2. Select the Setup button.
3. In the PDU settings dialog box, chose a selection from the Outlet State On PDU Startup dropdown menu:
•
On: this will turn all outlets on upon initial startup
•
Off: this will turn all outlets off upon initial startup
•
Last Known: this will restore all outlets to the last known power states before the device was shut
down
Setting the Outlet Default State for Individual Outlets on EN2000 and EN6000 Series PDUs
The EN2000 and EN6000 Series PDUs allow you to determine the initial power status of an individual outlet
upon power up.
1. Expand the Outlets folder. Select the individual outlet from the PDU Explorer.
2. Select an option from the dropdown in the State on Startup Row:
•
On: this will turn an outlet on upon initial startup
•
Off: this will turn an outlet off upon initial startup
•
Last Known: this will restore outlets to the last known power states before the device was shut down
Switching an Outlet On or Off on EN2000 and EN6000 Series PDUs
(This is only applicable to outlet-switched PDUs).
•
Outlets on the switched PDU models in the EN2000 series and the EN6000 series are easily switched
on, switched off, or power cycled. This action does require that the Switch Outlet permission is
enabled in the user profile. (By default, admins and standard users have this permission).
1. Select the Outlet Power Management Folder from the Enlogic PDU Explorer.
2. In the Outlet Power Management Panel, select the outlet that must be switched on, switched off, or reboot.
3. Select the desired Power Control from the dropdown menu.
4. Select Apply.
Setting the Outlet Power On/Off Delay for EN2000 and EN6000 Series PDUs.
(This is only applicable to outlet-switched PDUs).
When the PDU is turned ON, outlets will consecutively power on from Outlet 1 to the highest available outlet
number. With the EN6000 series PDUs.
1. Select the Outlet Power Management Folder from the PDU Explorer.
2. Select the outlet(s) for which to set a delay.
3. Using the Power Control dropdown menu, select the control: On Delayed or Off Delayed.
4. Select Apply.
5. To configure the length of delay, select the Outlet name from the PDU Explorer.
6. In the On Delay or Off Delay row, enter the length of delay (in seconds) in the Value column.
To Edit the length of reboot duration of individual outlets,
1. Select the outlet from the Outlet Power Control Folder.
2. Enter a value (between 5 and 60 seconds) in the Reboot Duration row.