www.enlogic.com
40
Section 6: Environmental Sensors
The EN Series PDU can monitor environmental conditions with Enlogic’s environmental sensors. Environmental Sensors are
connected to the EN Series PDU through the RJ45 connection or through the Sensor Input Hub which can connect up to three
additional environmental sensors. The following environmental sensors are available:
•
Alarm Beacon
•
Temperature Sensor
•
Temperature and Humidity Sensor
•
(3) Tempe (1) Humidity Sensor
•
Sensor Input Hub
•
Door Switch Sensor
•
Dry Contact Cable
•
Spot Fluid Leak Sensor
•
Rope Fluid Leak Sensor
•
Smoke Sensor
Sensor Overview
For detailed specifications of each environmental sensor refer to Appendix C of this manual.
Sensor
SKU
Description
Alarm Beacon
9101
Enlogic’s Alarm Beacon is designed to create a visible alarm notification of a
trouble condition (or other user-defined situation) in an effort to notify personnel
quickly and efficiently. The Alarm Beacon can be extended (up to 30.5 m) using a
standard RJ-45 coupling.
Temperature Sensor
9102
The temperature sensor monitors the temperature in the Data Center (or Network
Closet) and transfers the information to the control center.
Temperature and
Humidity Sensor
9103
The Temperature and Humidity Sensor Monitors the temperature and Relative
Humidity in the Data Center and transfers the data to the control center.
3-Tempe
1-Humidy Sensor
9105
The (3) Temperature and (1) Humidity Sensor Monitors 3 temperature probes and 1
Relative Humidity probe in the Data Center and transfers the data to the control center.
Sensor Input Hub
9106
Allows 3 environmental sensors to be connected through one port.
Door Switch Sensor
9109
Enlogic’s Door Switch Sensor is designed to send an alarm or notification signal
when the door on which is installed had been opened more than 10mm. This
provides added security.
Dry Contact Cable
9110
Enlogic’s Dry Contact Cable is designed to monitor conditions such moisture
detection, motion, door sensor, and access through external dry contact sensors.
This allows for convenient control of vital datacenter and IT equipment with
minimal effort quickly and efficiently. The dry contact cable can be extended (up
to 30.5 m) using a standard RJ-45 coupling.
Spot Fluid Leak Sensor
9111
Spot fluid sensor monitors a remote location for the presence of any liquid with
resistivity of less than 2M Ohms per cm (including distilled water) and transfers
the data to the control center. Note: Always place the spot fluid sensor on the
provided insulator sheet to avoid shorting the contacts. The Spot fluid sensor can
short when the sensor is placed on a metal surface, or other material that may be
conductive and grounded (such as cement floor that is wet).
Rope Fluid Leak Sensor
9112
The Rope Fluid Leak Sensor monitors for early detection of liquid with a resistiv
-
ity of less than 2M Ohms per cm (including distilled water) in the monitored area
along the entire length of the rope.