background image

 

 

 

ENMET

 Corporation 

PO Box 979 

Ann Arbor, MI 48106-0979 

www.enmet.com

  

Manual Part Number 
80003-093 

MCN-13-011, 12/20/13 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EX-5130-IS 

Toxic Gas 

Sensor/Transmitter 

Manual 

Summary of Contents for EX-5130-IS

Page 1: ...ENMET Corporation PO Box 979 Ann Arbor MI 48106 0979 www enmet com Manual Part Number 80003 093 MCN 13 011 12 20 13 EX 5130 IS Toxic Gas Sensor Transmitter Manual...

Page 2: ...ier Replacement 11 6 0 REPLACEMENT PART NUMBERS 12 7 0 WARRANTY 12 List of Figures and Tables Figure 1 EX 5130 IS Features 2 Figure 2 EX 5130 IS Mounting Dimensions 3 Figure 3 Terminal Positions EX 51...

Page 3: ...and after you have received written acknowledgment of the damage from the carrier contact ENMET Customer Service for return authorization and further instructions Have your Purchase Order and Sales O...

Page 4: ...ment maintenance functions The switch locations are indicated by MENU and SELECT A magnetic field pulse is applied by momentarily putting the end of the magnet in proximity to the switch and then remo...

Page 5: ...ansmitters Also take into consideration environmental factors when deciding on S T location Avoid locations where the S T may be damaged by liquid immersion excessive heat or other know hazards Also t...

Page 6: ...mA out 4 RS 485 D 5 RS 485 D Contact ENMET for Modbus Address information Figure 3 Terminal Positions EX 5130 IS Sensor Transmitter When wiring is complete reassemble the EX 5130 IS Use caution when...

Page 7: ...furthest right character in the display may flash a letter indicating the instrument status See the Section 4 1 2 below 4 1 Start up Typical Start Up When power is supplied to the EX 5130 IS the S T w...

Page 8: ...isplay indicates Alarm 1 Set point Tap the magnet over the MENU button Display indicates Alarm 2 Set point Tap the magnet over the MENU button No Function for the SELECT button in this mode Display in...

Page 9: ...Mode Measurement of target gas Hold the magnet over MENU switch for 2 5 seconds to enter the Maintenance Menu The Power Fault LED will flash Green Red to indicate the EX 5130 IS is in Maintenance Mod...

Page 10: ...st quarterly calibration of the EX 5130 IS transmitters Calibration equipment is available from ENMET Corporation to calibrate the EX 5130 IS sensor transmitters A calibration adapter will have a fitt...

Page 11: ...nal level 3 Attach the associated calibration gas cylinder to the regulator and calibration cover See to Figure 3 4 Open the valve to apply the calibration gas to the sensor 5 Watch for the signal lev...

Page 12: ...anges digit indicated by underscore cursor The SELECT switch locks underscored digit and moves to next digit See Section 5 2 2 SELECT mA Span MENU SELECT 100 To change mA Span set point Tap the MENU s...

Page 13: ...has been installed it is suggested to allow the sensor to stabilize for 24 hours A Factory calibration must be performed After entering the Maintenance menu advance to the Zero menu Then while viewing...

Page 14: ...FedEx Ground If an expedient means of transportation is requested during the warranty period the customer is responsible for the difference between the most economical means and the expedient mode EN...

Page 15: ...processing delays ENMET charges a one hour minimum billing for all approved repairs with additional time billed to the closest tenth of an hour All instruments sent to ENMET are subject to a minimum...

Page 16: ...nt Terms K COD Check one K VISA MasterCard______________________ ________ ________ Card number Expiration Card Code K American Express______________________ ________ ________ Card number Expiration Ca...

Reviews: