3.0 Installation of the EX-5175-EC 

C

AUTION

:

 

Area must be declassified during installation.

 

The 

ENMET

 

EX-5175-EC 

gas sensor/transmitter (S/T) is a 3-wire, 24 

V

DC

,

 4-20 mA S/T for the detection of toxic 

gas.  The S/T is meant to be used in conjunction with an appropriate power supply and controller.  The 

ENMET

 EX-

5175-EC 

sensor/transmitter has been designed and approved to be used in a Class I, Div. 1, Groups B, C, D, classified 

areas.  The approval was issued by CSA International.  Appropriate wiring, conduit and fittings are required for proper 
installation in a explosion proof rated environment. 

C

AUTION

:

 Since the sensor/transmitter detects gas only at the sensor location, pay attention to the possible sources of 

gas, the density of the gas, locations where the gas may be confined and locations where the gas may damage 
or injure property or personnel, when choosing locations of sensor/transmitters. 
Also, take into consideration environmental factors when deciding on S/T location. Avoid locations where the 
S/T may be damaged by liquid immersion, excessive heat or other know hazards.  Also, take precautions to 
insure condensation inside of the conduit does not enter the S/T. 

3.1 Mounting the EX-5175-EC Enclosure 

Mount the enclosure, using the two mounting holes provided see 

Figure 2

.  Pay particular attention to the source and 

density of the gas being detected when choosing the location.  Mount the S/T near the ceiling for lighter than air gases 
/vapors and near the floor for heavier then air gas/vapors.  Contact 

ENMET

 if you have questions regarding your 

application. 

C

AUTION

:

 

Before connecting S/T to controller remove the power source to controller.  Failure to do so may cause 

damage to sensitive components.

 

 

Figure 2: EX-5175-EC Mounting Dimensions  

Optional 
Conduit fitting  
Typically: ½

 NPT female 

Mounting Holes 

2 places, 0.313

 

Sensor 

Sensor/Transmitter 

Enclosure Side View 

Sensor 

½

 NPT female 

Sensor/Transmitter 

Enclosure Top View 

Me
nu

Sel
ect

Summary of Contents for EX-5175-EC

Page 1: ...ENMET Corporation PO Box 979 Ann Arbor MI 48106 0979 www enmet com Manual Part Number 80003 099 MCN 13 008 11 06 13 EX 5175 EC Sensor Transmitter Manual...

Page 2: ......

Page 3: ...acement 11 6 0 REPLACEMENT PART NUMBERS 12 7 0 WARRANTY 12 List of Figures and Tables Figure 1 EX 5175 EC Features 2 Figure 2 EX 5175 EC Mounting Dimensions 3 Figure 3 Terminal Positions EX 5175 EC Se...

Page 4: ......

Page 5: ...and the contents After the inspection and after you have received written acknowledgment of the damage from the carrier contact ENMET Customer Service for return authorization and further instruction...

Page 6: ...ment maintenance functions The switch locations are indicated by MENU and SELECT A magnetic field pulse is applied by momentarily putting the end of the magnet in proximity to the switch and then remo...

Page 7: ...oosing locations of sensor transmitters Also take into consideration environmental factors when deciding on S T location Avoid locations where the S T may be damaged by liquid immersion excessive heat...

Page 8: ...ct the wires from the controller power supply to the supplied J4 plug then attach to J4 terminal See Figure 3 for locations J4 PLUG TERMINAL TO CONTROLLER WIRING Position Function 1 24 VDC power 2 GND...

Page 9: ...hen power is supplied to the EX 5175 EC the S T will display the following sequence of information NOTE Software revision may cause variations of display output Example of Display Function The instrum...

Page 10: ...on below Display Measurement of the target gas Tap the magnet over the MENU button Display indicates Alarm 1 Set point Tap the magnet over the MENU button Display indicates Alarm 2 Set point Tap the m...

Page 11: ...of target gas Hold the magnet over MENU switch for 2 5 seconds to enter the Maintenance Menu The Power Fault LED will flash Green Red to indicate the EX 5175 EC is in Maintenance Mode To exit the main...

Page 12: ...C transmitters Calibration equipment is available from ENMET Corporation to calibrate the EX 5175 EC sensor transmitters A calibration adapter will have a fitting for the gas cylinder on one side and...

Page 13: ...Figure 4 3 Open the valve to apply the calibration gas to the sensor wait approximately 120 seconds 2 minutes 4 Tap the SELECT switch to perform a Span procedure The display will alternate between th...

Page 14: ...anges digit indicated by underscore cursor The SELECT switch locks underscored digit and moves to next digit See Section 5 2 2 SELECT mA Span MENU SELECT 100 To change mA Span set point Tap the MENU s...

Page 15: ...d Assembly into the sensor housing cover Reassemble the sensor housing Turn On the sensor transmitter After the new sensor has been installed it is suggested to allow the sensor to stabilize for 24 ho...

Page 16: ...edEx Ground If an expedient means of transportation is requested during the warranty period the customer is responsible for the difference between the most economical means and the expedient mode ENME...

Page 17: ...processing delays ENMET charges a one hour minimum billing for all approved repairs with additional time billed to the closest tenth of an hour All instruments sent to ENMET are subject to a minimum...

Page 18: ......

Page 19: ..._____________ Payment Terms COD Check one VISA MasterCard______________________ ________ ________ Card number Expiration Card Code American Express______________________ ________ ________ Card number...

Page 20: ......

Reviews: