Technical Specifications 

Technical Specifications

Device model name:

DC GW-V3.1

Power supply

5 V DC , 2 A

Dimensions (HxWxD):

26 x 85 x 103 mm

Weight:

195 g (without Power Supply)

Operating temperature:

5 to 35 °C

Electric consumption (max):

3,0 W

Connections:

1x LAN(RJ45), 1x Antenna connector, 1x USB

RF band:

868MHz

Range:

Without obstacles up to 40m

Features

DCG Configurator

Configuration via Web-Interface

Import/Export of Configuration Data

Yes

SoftwareStack

DC OS 5, providing Simple String, Restful JSON based 
commands

Symbols

The conformity of the product with the applicable EC directives.

RoHS

Tested in accordance with EU directive 2011/65 / EU - "Restriction of certain Hazardous 
Substances" - restriction of individual hazardous substances.

Protection class III - Safety extra low voltage according to EN 61140

Operation via safety transformer, double insulation between the power circuit and output 
voltage. 

Limits: 50V AC - AC / 120V DC - DC

WEEE Directive (Waste Electrical and Electronic Equipment)

According to the European Directive 2002/96 / EC and 2012/19 / EU 

Disposal of the device is not in household waste but at an appropriate electronic waste 
collection point. 

WEEE-Reg.-Nr. DE 83788620

Device is to be used for the designated purpose only.

Device is to only be used with the provided power supply.

Areas of application

The device is only to be used in the designated areas of application: Application: Interior; 
Storage and Use: Dry

Tested in accordance with EMC Directive EN 61000

EN 61000-6-1 (Immunity to interferences Residential, ...) (Immunity for industrial 
environments) 

EN 61000-6-3 (interference emission living area, ...) 

EN 61000-6-4 (Interference emission industrial environments)

Digital Concepts GmbH, Wankelstraße 1, 70563 Stuttgart, Germany 

info@digital-concepts.eu

www.digital-concepts.eu

+49 (0)711 508 704-0 

Summary of Contents for DC-GW/EO-IP V3.1

Page 1: ...ing 3 6 2 Rail Mounting 3 6 3 Positioning variant 3 7 Hardware installation 3 8 Commissioning 3 8 1 Device detection and access 3 8 2 Accessing the Web Interface 4 8 2 1 Gateway detection in Windows systems via UPNP 4 8 2 2 Gateway detection via Bonjour 4 8 2 3 Device Setting via DHCP Server Entries 4 8 3 Login DCG Configurator 4 8 4 DCG Configurator 5 9 Troubleshooting 5 10 EU Declaration of Conf...

Page 2: ...urpose The device is only suitable for indoor use Avoid exposing the device to moisture dirt or dust Avoid direct sunlight and other sources of heat FFAQs and downloads can be found at www enocean gateway eu In case of technical problems please contact our support support digital concepts eu 2 Functionality The primary function of this product is to act as a communication bridge between EnOcean Wi...

Page 3: ...ectrical switches sockets or cables 6 1 Wall mounting The holes in the housing can be used to fix the device to a wall 6 2 Rail Mounting Attach the DIN rail mounting clip to the back of the gateway with the supplied screw D 6 3 Positioning variant Remove the covers from the supplied self adhesive feet D and attach them to the corners of the bottom of the Gateway 7 Hardware installation Screw the a...

Page 4: ...work administrator if you have problems accessing the device 8 2 2 Gateway detection via Bonjour Bonjour service is recommended when using MacOS or iOS environments Your network environment must allow Bonjour communication If you have difficulty finding the gateway contact your network administrator The gateway can be accessed by opening a web browser and entering the default name dcgw followed by...

Page 5: ... the power supply for at least 20 seconds and reconnect the device If the gateway is still not responding check all cable connections to the device Make sure that the network activity LEDs indicate normal operation If EnOcean devices are not working reliably try moving the gateway to another location or removing sources of potential RF interference 10 EU Declaration of Conformity Digital Concepts ...

Page 6: ...g to EN 61140 Operation via safety transformer double insulation between the power circuit and output voltage Limits 50V AC AC 120V DC DC WEEE Directive Waste Electrical and Electronic Equipment According to the European Directive 2002 96 EC and 2012 19 EU Disposal of the device is not in household waste but at an appropriate electronic waste collection point WEEE Reg Nr DE 83788620 Device is to b...