1.2 Typical Applications
•
Building installation
•
Industrial automation
•
Consumer electronics
Key applications are wall-mounted flat rocker switches with 1 or 2 rockers, as well as handheld
remote controls with up to 4 single pushbuttons. Because the RF transmitters are self-powered
(no batteries), maintenance-free RF systems are possible.
1.3 Features Overview
Power supply
: ............................................................. Electro-dynamic Power Generator
(power generation by rocker operation)
Frequency / transmission power
:....................... 315.0 MHz / typ. 3dBm at antenna input
Modulation type / data rate
: ................................................................. ASK / 125 kbps
Antenna
:........................................................external whip antenna 26.8 cm,
ø
1.3
±
0.1
mm
Transmission range
: ..........................................up to 200 m free field, up to 30m indoor
Telegram packet length (sub-telegram)
:................................................ 0.7 ms +/-5%
No. of (redundant) packets
: ................................... 3 – 5 (depending on residual energy),
3 packets within about 20 ms, delay effected at random
Number of channels
:................................................ 2 channels with 4 action states each
(upper/lower contact nipple is pressed/released)
Telegram type
: ........................................................................................RPS of type 2
(allows interpretation of operating two buttons simultaneously)
Device identifier
: ............................................ individual 32-bit ID (factory programmed)
1.4 Mechanical Interface
Device dimensions
: ................................................................ 40.0 x 40.0 x 11.2*) mm
*) Height without label
Device weight
: .............................................................................................20 g ± 1g
Energy bow travel / operating force
: ...................................... 1.8 mm / approx. 7 N *)
*) at room temperature, only one energy bow may be actuated at the same time!
Restoring force at energy bow
: .................................................................. 0.5N to 4N
For the correct function of the application, the specified minimal restoring force of 0.5N must be considered!
Number of operations
: ...... typ 50.000 actuations tested according to VDE 0632 / EN 60669
Cover material
: .................................................................................. Hostaform (POM)
Energy bow material
:............................................................................ PBT (50% GV)
©EnOcean GmbH, W. Heller
Page 5 of 19