Software Release: [App: 02.09.10039.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version:
2.9.23042; BTL: 02.09.10015.00]
Section 40
19
00-02-0996
2019-06-13
12. Set the range of the transducer on the high side then press
[Enter].
(i.e., 0-10ft transducer would
show 4mA at 0 ft. and 20mA at 10 ft.)
13. Press
[Back]
twice to return to the main menu.
14. Utilize the Up and Down arrows to select
Advanced Engine Settings
then press
[Enter]
.
15. Utilize the Up and Down arrows to select
Warnings and Shutdowns
then press
[Enter].
16. Utilize the Up and Down arrows to set the
High and Low Level
warnings and shutdowns.
17. Press the
[Menu]
key to exit the Menu Setup screens.
Setting up to Auto Start on Flow
1. Access
Menu/Application Configuration.
Press the down arrow to
Auto Start/Stop Function
then
press
[Enter]
.
2. Utilize the Up and Down arrows to select
Flow Transducer
then press
[Enter].
3. Utilize the Up and Down arrows to select
Flow Transducer
in the main application configuration menu.
4. Complete the parameters that apply (Start/Stop Flow and Flow Maintain Type. See Menu Glossary
for explanation of settings).
5. Press
[Back]
twice and access
Input_Output/Analog Inputs.
6. Select the Analog Input to modify for the Flow transducer.
7. Assign 4-20mA Flow Rate as the function for the selected Analog Input.
8. Press
[Back]
once to return to the Analog Input menu.
9. Press the arrow up or arrow down key to select
Sensor Setup
then press
[Enter]
.
10. Select Flow Rate to set up then press
[Enter]
.
11. Set the offset of the 4mA if needed to calibrate the low side then press
[Enter]
.
12. Set the range of the transducer on the high side then press
[Enter].
(e.g., 0-20,000 gal/min transducer
would show 4mA at 0 gal/min and 20mA at 20,000 Gal/min.)
13. Press
[Back]
twice to return to the main menu.
14. Utilize the Up and Down arrows to select
Advanced Engine Settings
then press
[Enter]
.
15. Utilize the Up and Down arrows to select
Warnings and Shutdowns
then press
[Enter].
16. Utilize the Up and Down arrows to set the
High and Low Flow
warnings and shutdowns.
17. Press the
[Menu]
key to exit the Menu Setup screens.
Setting up to Auto Start on Clock
NOTES:
1)
Ensure the correct date and time are established in the System menu prior to
establishing the Auto Start on Clock settings.
2)
The Clock start timer is independent of other auto start start/stop functions. When
started from the clock the controller will shut down the engine from the clock.
1. Access
Menu/Start_Stop Timers
, and select the first Start/Stop Timer.
2. Select Start Day 1 and then select the appropriate day or Daily.
3. Select Start Time 1 and establish the hour, minute and second to start.
4. Establish the Stop Day and Time as in steps 2-3.
5. Press the
[Menu]
key to exit the menu setup screens.
NOTE:
The MPC-20 has the ability to establish seven different Start/Stop dates and
times. If desired, repeat steps 1-3 for subsequent Timers.
Setting up to Auto Start on Temperature
1. Access
Menu/Application Configuration.
Press the down arrow to
Auto Start/Stop Function
then
press
[Enter]
.
2. Utilize the Up and Down arrows to select
Temperature Transducer
then press
[Enter].