Software Release: [App: 02.09.10039.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version:
2.9.23042; BTL: 02.09.10015.00]
Section 40
30
00-02-0996
2019-06-13
Clear Active ECU Fault Codes
–
(High Security): allows the operator to clear all active faults from
the engine ECU. This setting should only be used by a qualified engine technician. All engine
manufacturers and models may not support this feature. This menu item is only shown if J1939 is
selected for the Engine Type.
Clear Stored ECU Fault Codes
–
(High Security): allows the operator to clear stored faults from the
engine ECU. This setting should only be used by a qualified engine technician. All engine
manufacturers and models may not support this feature. This menu item is only shown if J1939 is
selected for the Engine Type.
Auto / Manual
–
(High Security): allows the operator to select two options related to Auto and Manual modes.
Manual Only
–
(High Security): allows the operator to lock out the auto mode of the controller when
set to Enable.
Factory set to Disable.
Power up Auto/Manual
–
(High Security):
allows the controller to power up in either manual or auto
mode of operation depending on the selection chosen.
Factory set to Manual.
Show Auto Start Confirmation
(High Security)
:
ensures the operator knows the controller is in
auto by making the operator accept the Auto mode on power up. This is only shown if Power Up
in Auto/Manual is set to Auto.
Factory set to Yes
Green LED
–
(High Security): allows the operator to set the green LED to illuminate when either in auto mode
or when the controller is in the Running Loaded state.
Factory set to Auto.
Restore Factory Defaults
–
(Medium Security): allows the operator to reset all menu settings set as defaults
from the last configuration loaded in the controller.
Set Internal Machine Hours
–
(High Security): allows the operator to set the machine hours. This setting is
visible when the Engine Type is set to Mechanical or when the ECU Hour Select is set to Internal.
Event History
–
(Medium Security):
View Event History
–
(Medium Security):
allows the operator to view history of the last 32 warnings
or shutdowns with date and time stamp.
Clear Event History
–
(High Security): allows the clearing of event history.
J1939 Shutdowns
–
(High Security): this parameter allows the user to set whether they want the controller
to help facilitate a shutdown for the engine if the ECU broadcasts a Red lamp (DM1 Shutdown) across the
CANbus. When set to ECU Only the controller will show the fault while completely relying on the engine
to shutdown the engine when the fault is broadcast on the CANbus. When set to Controller and ECU the
controller will turn off the ECU enable output when a red lamp status is broadcast on the CANbus.
Factory
set to Controller & ECU
.
Engine Settings
(Low Security)
Engine Type
–
(High Security): allows the selection of J1939 or Mechanical. If Mechanical is chosen, some
parameters associated with J1939 will no longer appear in the menu.
Factory set to J1939.