Software Release: [App: 02.09.10039.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version:
2.9.23042; BTL: 02.09.10015.00]
Section 40
34
00-02-0996
2019-06-13
Post Crank Lockout 1
–
(Medium Security):
Factory set to Low Oil Pressure
Post Crank Lockout 2
–
(Medium Security):
Factory set to High Engine Temperature
Post Crank Lockout 3
–
(Medium Security):
Factory set to Disabled.
Post Crank Lockout 4
–
(High Security):
Factory set to Disabled
.
Post Crank Lockout 5
–
(HIgh Security):
Factory set to Disabled.
Post Warm-up Lockout Setup
–
(Medium Security): allows a delay that begins timing following the
warm-up delay. During this delay, the selected functions (Warnings and Shutdowns) are ignored.
When this delay expires, the selected functions are armed. During the duration of this delay, the
selected functions can cycle from active to not active and not reset the delay.
Post Warm-up Lockout Time
–
(Medium Security):
Factory set to 00.00.00
Post Warm-up Lockout 1
–
(Medium Security):
Factory set to Disabled.
Post Warm-up Lockout 2
–
(Medium Security):
Factory set to Disabled.
Post Warm-up Lockout 3
–
(Medium Security):
Factory set to Disabled.
Post Warm-up Lockout 4
–
(High Security):
Factory set to Disabled.
Post Warm-up Lockout 5
–
(High Security):
Factory set to Disabled.
Bubble Lockout Setup
–
(Medium Security): setup for a delay that begins timing when the selected
functions are active. If the selected functions are removed during this delay, the delay resets to zero.
If the selected functions remain active throughout this delay, the selected action for the parameter will
occur.
Bubble Lockout Time
–
(Medium Security):
Factory set to 00.00.00
Bubble Lockout 1
–
(Medium Security):
Factory set to Disabled.
Bubble Lockout 2
–
(Medium Security):
Factory set to Disabled.
Bubble Lockout 3
–
(Medium Security):
Factory set to Disabled.
Bubble Lockout 4
–
(Medium Security):
Factory set to Disabled.
Bubble Lockout 5
–
(Medium Security):
Factory set to Disabled.
Warnings and Shutdowns
–
(Low Security):
establish parameters for the:
Low Fuel Level Warning
–
(Low Security): sounds a warning when the fuel level reaches the set
lower limit parameter.
Factory set to 10%
Low Fuel Level Shutdown
–
(Medium Security): shuts down the engine when the fuel level reaches
the set lower limit parameter.
Factory set to 5%
High Battery Warning
–
(Low Security): sounds a warning when the charge on the battery reaches
the set higher limit parameter.
Factory set to 15.0 V.
Low Battery Warning
–
(Low Security): sounds a warning when the charge on the battery reaches
the set lower limit parameter.
Factory set to 10.0 V.
Weak Battery Warning
–
(Low Security): sounds a warning when the charge on the battery reaches
the set parameter for weakness.
Factory set to 6.0 V.
LOP High Speed
–
(High Security): speed setting in which the Low Oil Pressure (LOP) will be active
at high speed.
Factory set to 2000 RPM.
LOP Warning/High Speed
–
(High Security): Low Oil Pressure (LOP) setting in which the controller
will provide a warning if dropping below at high speed.
Factory set to 35.00 psi.