Section 40
36
00-02-0996
2019-06-13
High Level Warning
–
(Medium Security): sounds a warning when the system level reaches the set
high limit parameter for system level. Selection only shown when an analog input is selected to monitor
System Level.
Factory set to 0.0 ft
.
High Level Shutdown
–
(Medium Security): shuts down the engine when the system level reaches
the set high limit parameter for system level. Selection only shown when an analog input is selected
to monitor System Level.
Factory set to 0.0 ft.
Low Level Warning
–
(Medium Security):
sounds a warning when the system level reaches the set
low limit parameter for system level. Selection only shown when an analog input is selected to monitor
System Level.
Factory set to 0.0 ft.
High Flow Warning
–
(Medium Security):
sounds a warning when the flow rate reaches the set high
limit parameter for flow rate. Selection only shown when an analog input is selected to monitor Flow
Rate.
Factory set to 0 gpm.
High Flow Shutdown
–
(Medium Security):
shuts down the engine when the flow rate reaches the
set high limit parameter for flow rate. Selection only shown when an analog input is selected to monitor
Flow Rate.
Factory set to 0 gpm.
Low Flow Warning
–
(Medium Security):
sounds a warning when the flow rate reaches the set low
limit parameter for flow rate. Selection only shown when an analog input is selected to monitor Flow
Rate.
Factory set to 0 gpm.
Low Flow Shutdown
–
(Medium Security): shuts down the engine when the flow rate reaches the set
low limit parameter for flow rate. Selection only shown when an analog input is selected to monitor
Flow Rate.
Factory set to 0 gpm.
High Discharge Pressure Warning
–
(Medium Security): sounds a warning when the discharge
pressure reaches the set high limit parameter for discharge pressure. Selection only shown when an
analog input is selected to monitor Discharge Pressure.
Factory set to 0.00 psi.
High Discharge Pressure Shutdown
–
(Medium Security):
shuts down the engine when the
discharge pressure reaches the set high limit parameter for discharge pressure. Selection only shown
when an analog input is selected to monitor Discharge Pressure.
Factory set to 0.00 psi.
Low Discharge Pressure Warning
–
(Medium Security):
sounds a warning when the discharge
pressure reaches the set low limit parameter for discharge pressure.
Selection only shown when an
analog input is selected to monitor Discharge Pressure.
Factory set to 0.00 psi.
Low Discharge Pressure Shutdown
–
(Medium Security):
shuts down the engine when the
discharge pressure reaches the set low limit parameter for discharge pressure.
Selection only shown
when an analog input is selected to monitor Discharge Pressure.
Factory set to 0.00 psi.
High Suction Pressure Warning
–
(Medium Security):
sounds a warning when the suction pressure
reaches the set high limit parameter for suction pressure. Selection only shown when an analog input
is selected to monitor Suction Pressure.
Factory set to 0.00 psi.
High Suction Pressure Shutdown
–
(Medium Security):
shuts down the engine when the suction
pressure reaches the set high limit parameter for suction pressure.
Selection only shown when an
analog input is selected to monitor Suction Pressure.
Factory set to 0.00 psi.