Section 40
41
00-02-0996
2019-06-13
Datcon Engine Temperature
VDO Engine Temperature
Murphy Fuel Level
– (ES2F)
VDO Fuel Level
Datcon Fuel Level
Murphy Oil Temperature
– (ES2T-250/300)
Datcon Oil Temperature
VDO Oil Temperature
Murphy Discharge Pressure
– (ES2P-100)
Murphy Suction Pressure
– (ES2P-100)
Datcon Pump Housing Temperature
Murphy Pump Housing Temperature
– (ES2T-250/300)
VDO Pump Housing Temperature
Murphy Pump Oil Temperature
– (ES2T-250/300)
Datcon Pump Oil Temperature
VDO Pump Oil Temperature
Murphy GearBox Pressure
– (Gear Box Pressure, Murphy PMK-400 Sensor)
Analog.Digital1
Index Coolant Level Probe Shutdown
0.5-4.5V Remote Throttle:
(0.5V = Min Engine Speed, 4.5V = Max Engine Speed, Remote
Throttle Digital Input must be active to allow analog to work properly)
4-20mA Remote Throttle:
(4mA = Min Engine Speed, 20mA = Max Engine Speed, Remote
Throttle Digital Input must be active to allow analog to work properly)
Model 12 Air Temp Sensor:
(Murphy 0-5V Model 12 preset Ambient Temp Sensor)
Sensor Setup
–
(Medium Security): (only appears when the analog inputs are configured. This sets the range
of sensors for 4-20mA or 0-5V senders.)
Oil Pressure
(0-5V) or (4-20mA)
Ambient Temp
(0-5V) or (4-20mA) by raising the minimum value (4mA or 0V) in the sensor
setup, a negative Ambient Temperature can be read by the Controller in Celsius or a
temperature below 32 degrees in Fahrenheit.
Coolant Temp
(0-5V) or (4-20mA)
Discharge Pressure
(0-5V) or (4-20mA)
Fluid Pressure
(0-5V) or (4-20mA)
Fuel Level
(0-5V) or (4-20mA)
Oil Temp
(0-5V) or (4-20mA)
Pump Housing Temp
(0-5V) or (4-20mA)
Pump Oil Temp
(0-5V) or (4-20mA)
Suction Pressure
(0-5V) or (4-20mA) by raising the minimum value (4mA or 0V) in the sensor
setup, a negative Suction Pressure can be read by the Controller.
Flow Rate
(4-20mA)
System Level
(4-20mA) Set mA per Ft
Discharge Pressure Units
–
(Medium Security): (only appears when discharge pressure is selected as on
analog input. This selection allows the operator to change the discharge pressure units and not the global
pressure units.)
Factory set to PSI.
Relay (1-6) and Digital (1-6) Outputs
–
(Medium Security):
the same parameters are used for both the Relay
and Digital Outputs.
Relay 1.
Factory set to Crank.
Relay 2.
Factory set to ECU Enable.
The controller will not transmit on the CAN bus when this
output is off.