Software Release: [App: 02.09.10039.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version:
2.9.23042; BTL: 02.09.10015.00]
Section 40
45
00-02-0996
2019-06-13
NOTE:
In order for linear auto throttle to work correctly the auto start/stop function and
auto throttle method need to be set to the same transducer type.
Auto Running Loaded Speed
–
(Medium Security): present when selecting Running Loaded as the Auto
Throttle Method. This will set the speed at which the controller will run in auto mode when in the Running
Loaded state.
Factory set to 2000 RPM.
Pressure Transducer
–
(Medium Security): only present when selecting Pressure Transducer in the Auto
Start / Stop Function or Auto Throttle Method.
Start Pressure
–
(Medium Security): present when selecting Pressure Transducer as the Auto Start /
Stop Function. When the pressure reaches this set point, an auto start will occur.
Factory set to 0
psi.
Stop Pressure
–
(Medium Security): present when selecting Pressure Transducer as the Auto Start /
Stop Function. When the pressure reaches this set point, an auto stop will occur.
Factory set to 0
psi.
Maintain Pressure
–
(Medium Security): the engine will be throttled between the min. and max. RPM
set points to maintain this pressure.
Factory set to 0 psi.
Deadband Pressure
–
(Medium Security): extends above and below the maintain set point. No
throttling occurs while the pressure is in the deadband.
Factory set to 0 psi.
Pressure Type
–
(Medium Security):
Suction / Discharge.
Discharge:
when the Auto Start/Stop is selected as Pressure Transducer and the Pressure Type is
set to
(Discharge)
, it is necessary to set the pressure to start on a low value
(falling ↓) then stop
on high value
(rising ↑) in order to work correctly. When the Auto Throttle Method is selected to
Pressure Transducer and the Pressure Type is set to
(Discharge)
, the controller throttles the
engine by increasing the RPM below the deadband and decreasing the RPM above the deadband
to maintain the desired level of Pressure.
Suction:
when the Auto Start/Stop is selected as Pressure Transducer and the Pressure Type is
set to
(Suction)
, it is necessary to set the pressure to start on a high value
(rising ↑) then stop on
low value
(falling ↓) in order to work correctly. When the Auto Throttle Method is selected to
Pressure Transducer and the Pressure Type is set to
(Suction)
, the controller throttles the engine
START/STOP LEVEL
LINEAR AUTO THROTTLE (LEVEL)
M
IN
/M
A
X
R
PM
1800 RPM
1200 RPM
1300 RPM
1400 RPM
1500 RPM
1600 RPM
1700 RPM
4.5'
4ft
7ft
6.5'
6'
5.5'
5'