Software Release: [App: 02.09.10039.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version:
2.9.23042; BTL: 02.09.10015.00]
Section 40
50
00-02-0996
2019-06-13
CAN Parameter Map
–
(High Security): allows an operator to enable or disable the CAN Parameter Map.
The CAN Parameter Map can be used in place of the Modbus map when using a CAN device to talk
to the controller for starting, stopping and control functions via telematics or another CAN based
system. See CAN Parameter Map Section below for definition of the mapping.
Factory set to
Disable.
CAN Baud Rate
–
(High Security):
Factory set to 250Kbps
10 Kbps
20 Kbps
50 Kbps
100 Kbps
125 Kbps
250 Kbps
500 Kbps
800 Kbps
1 Mbps
Passcodes
(High Security)
This menu allows the operator using the High Security Passcode to see the three 4-digit passcodes for Low,
Medium and High security. This is a visual menu only.
Load Configuration
(High Security)
NOTE:
It is essential that the USB Drive is formatted to a FAT file system before using to
load software. If the drive is not formatted to FAT and left in another format the file may
not load correctly.
This menu allows the MPC-20 operator using the High Security passcode to select a file from a USB drive
plugged into the programming harness for the controller. Once the files are stored on the drive after
generated in PowerVision for Controllers the file will show as long as the software was for the MPC-20
hardware and has the file extension .gcibin. Once the file is found it will show in the screen. Follow directions
on the screen to load desired file. The screen will turn off then all three LEDs will come on then the Amber
LED will begin flashing. Once the file is finished loading the Green LED stays on stead while the Amber and
Red LEDs flash. The USB drive can now be removed to initiate a reboot of the controller or simply cycle
power off then back on.
NOTE:
If the file does not fully load due to the file being corrupt, the controller turned off
during installing file, or the USB drive removed during drive the operator will be required to
load a file created for the MPC-20 named configurationFull.gcibin to recover the controller
from its bootloader mode. Once this is done the operator will be able to load a file from the
menu again following power up.