Software Release: [App: 02.09.10039.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version:
2.9.23042; BTL: 02.09.10015.00]
Section 40
53
00-02-0996
2019-06-13
15 = Reserved
Reserved
40011
Read Only
Actual System Level (50.5 ft will read 505)
Feet
40012
Read & Write Modbus Engine Start/Stop Auto Mode Only (Stop = 0, Start = 1)
(0 or 1)
40013
Read & Write Maximum Engine Speed Setpoint
RPM
40014
Read Only
Actual Ambient Temp
Celsius
40015
Read & Write Auto/Manual Mode (Manual = 0, Auto = 1)
(0 or 1)
40016
Read & Write Running Loaded Speed in Auto Setpoint
RPM
40017
Read & Write Manual Only (Manual Only Enabled = 1, Disabled = 0)
(0 or 1)
40018
Read & Write Prestart 1 Auto Only
(Prestart Auto Only = 1, Prestart Auto & Manual = 0)
(0 or 1)
40019
Read & Write Prestart 2 Auto Only
(Prestart Auto Only = 1, Prestart Auto & Manual = 0)
(0 or 1)
40020
Read Only
J1939.Actual Engine Torque
Percent
40021
Read Only
Reserved
Reserved
40022
Read Only
J1939.Diesel Particulate Filter Outlet Temperature
Celsius
40023
Read Only
J1939.Diesel Particulate Filter Intake Temperature
Celsius
40024
Read Only
J1939.Exhaust Temperature
Celsius
40025
Read Only
J1939.Engine Exhaust Manifold Bank 1 Temperature
Celsius
40026
Read Only
J1939.Boost Pressure
kPa
40027
Read Only
J1939.Engine Fuel Temperature
Celsius
40028
Read Only
J1939.Engine Intercooler Temperature
Celsius
40029
Read Only
J1939.Diesel Particulate Filter Ash Load Percent
Percent
40030
Read Only
J1939.Diesel Exhaust Fluid Tank Temperature
Celsius
40031
Read Only
J1939.Engine Fuel Delivery Pressure
kPa
40032
Read Only
J1939.Barometric Pressure
kPa
40033
Read Only
J1939.Air Filter Diff. Pressure
kPa
40034
Read Only
J1939.Exhaust Gas Temperature
Celsius
40035
Read Only
J1939.Hydraulic Pressure
kPa
40036
Read Only
J1939.Hydraulic Temperature
Celsius
40037
Read Only
J1939.Diesel Particulate Filter Active Regeneration Status: The
following is a description of enumeration values.
Numerals
0 = Not Active
1 = Active
2 = Regeneration Needed
3 = Not Available
40038
Read & Write System Level Engine Start (Auto) (50.5 ft will read 505)
Feet
40039
Read & Write System Level Engine Stop (Auto) (50.5 ft will read 505)
Feet
40040
Read & Write System Level Maintain Value (Auto) (50.5 ft will read 505)
Feet
40041
Read & Write Flow Rate Start
US Gal/Min
40042
Read & Write Flow Rate Stop
US Gal/Min
40043-40044
Read Only
Actual Discharge Pressure
kPa
40045-40046
Read & Write Pressure Engine Start (Auto)
kPa
40047-40048
Read & Write Pressure Engine Stop (Auto)
kPa
40049-40050
Read & Write Pressure Maintain Value (Auto)
kPa
40051-40200
Read Only
Reserved
Reserved
40201
Read Only
Version.App.1
Numerals
40202
Read Only
Version.App.2
Numerals
40203
Read Only
Version.App.3
Numerals