Software Release: [App: 02.09.10039.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version:
2.9.23042; BTL: 02.09.10015.00]
Section 40
37
00-02-0996
2019-06-13
Low Suction Pressure Warning
–
(Medium Security):
sounds a warning when the suction pressure
reaches the set low limit parameter for suction pressure. Selection only shown when an analog input
is selected to monitor Suction Pressure.
Factory set to 0.00 psi.
Low Suction Pressure Shutdown
–
(Medium Security):
shuts down the engine when the suction
pressure reaches the set low limit parameter for suction pressure.
Selection only shown when an
analog input is selected to monitor Suction Pressure.
Factory set to 0.00 psi.
High Pump Housing Temp. Warning
–
(Medium Security): sounds a warning when the pump
housing temperature reaches the set high limit parameter for pump housing temperature.
Selection
only shown when an analog input is selected to monitor Pump Housing Temperature.
Factory wet to
32 F.
High Pump Housing Temp. Shutdown
–
(Medium Security):
shuts down the engine when the pump
housing temperature reaches the set high limit parameter for pump housing temperature.
Selection
only shown when an analog input is selected to monitor Pump Housing Temperature.
Factory set to
32 F.
High Pump Oil Temp. Warning
–
(Medium Security):
sounds a warning when the pump oil
temperature reaches the set high limit parameter for pump oil temperature.
Selection only shown when
an analog input is selected to monitor Pump Oil Temperature.
Factory set to 32 F.
High Pump Oil Temp. Shutdown
–
(Medium Security):
shuts down the engine when the pump oil
temperature reaches the set high limit parameter for pump oil temperature. Selection only shown when
an analog input is selected to monitor Pump Oil Temperature.
Factory set to 32 F.
Throttle Menu
(Medium Security)
Engine Throttle Type
–
(High Security):
allows the selection of J1939 TSC1, Pulse Inc/Dec, Analog 0-5VDC,
or None as the throttle type for the engine.
Factory set to J1939 TSC1.
J1939 TSC1
(High Security):
this setting will be used when an electronic engine is used for J1939
Throttling. (Verify with Engine Dealer this type of throttling is accepted on the specific engine.)
Pulse Inc/Dec
(High Security):
this setting will be used when throttling a mechanical engine, using a
throttle actuator and also an electronic engine using digital pulses into the ECU for throttling.
Analog 0-5 VDC
(High Security):
this setting will be used for throttling an electronic engine utilizing
0-5V output.
None
(High Security):
this setting will be used when the controller is not used to throttle the engine.
This setting will hide target speed on the main screen to only display actual engine speed.
Thomson
(High Security): this setting will be used when throttling a mechanical engine, using a
Thomson Throttle Linear Actuator via CAN communications.
Separate TSC1 Source Address
(High Security): allows the user to set a separate source address for
TSC1 throttling from the controller’s claim address. This should only be done if the service technician knows
this to be true.
Factory set to Disabled.
TSC1 Source Address
(High Security): allows setting TSC1 throttle to be sent from a source address
separate than the controller claim address. (Only appears when Separate TSC1 Source Address is set to
Enabled).