Software Release: [App: 02.09.10039.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version:
2.9.23042; BTL: 02.09.10015.00]
Section 40
49
00-02-0996
2019-06-13
Tuesday
Wednesday
Thursday
Friday
Saturday
Daily
Off*
Start Time:
format of HH:MM:SS
Stop Day:
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Daily
Off*
Stop Time:
format of HH:MM:SS
Communication
(High Security)
PVA Gauge:
this function will be used if utilizing PVA Gauges on the RS485 Communications Port.
Modbus:
this function will be used if using a SCADA or telemetry device for polling the Modbus
register list on the RS485 Communications Port. See Modbus Register Map.
Factory
Default.
Slave Address
–
(High Security): the RS485 Modbus slave node number.
Factory set to 1
.
Serial Setup
–
(High Security):
allows the operator to change the controller’s RS485 serial
communication settings.
Baud Rate
–
(High Security):
Factory set to 19200
9600
19200
38400
57600
115200
Stop Bits
–
(High Security):
Factory set to 1
0
1
2
Parity
–
(High Security):
Factory set to None
None
Odd
Even
PVCAN Backlight Enable
–
(High Security): allows the MPC-20-R2 to control the backlights of the
PVCAN gauges when used with the MPC-20-R2.
Factory set to Off
.
CAN Termination
–
(High Security): allows the operator to enable or disable the
controller’s internal 120
ohm terminating resistor. This should be enabled if the MPC-20-R2 is located at the end of the CAN
bus and the end terminating resistor is not used in the harness.
Factory set to Enable.