The keypad on the MPC-20-R2 is comprised of 11 tactile buttons. This section describes the functions of
each button.
The buttons have the following functions:
•
Start Key
– allows the operator to start sequence in Manual Mode or initiate an auto start
sequence when in Auto Mode.
•
Stop Key
– allows the operator to initiate the stop sequence in either mode of operation.
A single button press in auto will initiate an auto stop. As a safety feature, when the stop
button is pressed twice or held (in auto mode), the controller will skip the cool-down state
and (upon shutting down) will place itself in manual mode to eliminate an auto crank
condition if the start signal remains present.
•
Auto Key
– allows the operator to change from Auto to Manual or Manual to Auto Mode.
The MPC-20-R2 requires an acknowledgement from the user to place in auto mode from
manual.
•
Alarm Silence Key
– allows the operator to temporarily silence the internal siren, common
alarm output and acknowledge active faults when an alarm or shutdown is present on the
controller.
•
Manual Throttle Increase Key
– allows the operator to manually increase the engine
speed in Manual Mode.
•
Manual Throttle Decrease Key
– allows the operator to manually decrease the engine
speed in Manual Mode.
•
Menu Key
– allows the operator to get into and out of the menu.
•
Back Key
– allows the operator to move back one step in the menu without saving a value.
•
Enter Key
– allows the operator to save a desired value or setting in the menu.
•
Up Key
– allows the operator to navigate up through the menu and page forward in the
main page views.
•
Down Key
– allows the operator to navigate down through the menu and page reverse on
the main page views.