Envoy-S Installation and Operation
2016 Enphase Energy Inc.
141-00031 Rev 01
15
Provide Power for the Envoy-S Metered (ENV-S-WM1-230)
The Envoy-S Metered (ENV-S-WM1-230) uses terminal blocks for power connections. It does not include
an AC power cord, and you
must
hard-wire it. When you hard-wire the Envoy-S outdoors, you must
install it in an IP54-rated, or better enclosure with conduit attachment. Use an appropriately rated
enclosure if hard-wiring indoors.
DANGER!
Risk of electric shock. Be aware that installation of this equipment includes risk of
electric shock. If you wire the Envoy-S at the sub-board, always de-energise the sub-board
before beginning wiring.
a.
Use a single-pole 20 A maximum circuit breaker for the supply wiring.
b.
Make sure supply wiring is 1.5mm
2
copper rated at 75 degrees C or better.
c.
Locate the screw on the left side of the terminal block door, and loosen it with a screwdriver to
unlock the door.
d.
Flip open the terminal block door and wire the line and neutral conductors as shown in the
diagram. Tighten terminal block screws to 0.56 Nm.
- Connect Line (active) to A
- Connect Neutral to N