CT Label
For Production as well as Consumption/PCS CTs, you must apply
the following label to each CT when the system is configured to use
PCS-based current limiting.
The available space on the CTs for labeling is as follows
Consumption/PCS CT (CT-200-SPLIT):
• Left side: 20mm(vertical) x 14mm (Horizontal)
• Back side: 20mm (vertical) x 20mm (Horizontal)
Production CT (CT-200-SOLID):
• 9mm(vertical) x 30mm(horizontal)
THE MAXIMUM CURRENT BACKFED BY THIS SYSTEM TO THE MAIN
PANEL MAY BE CONTROLLED ELECTRONICALLY. REFER TO MANU-
FACTURER’S INSTRUCTIONS FOR MORE INFORMATION
PCS CONTROLLED CURRENT SETTING: ___________ AMPS
Manual Override Label
This is to be applied to be above (north of) the manual override switch
on the Enpower deadfront.
M6 screws and filler plates
During Enpower installation, after sliding in Enpower on the wall-
mount bracket shelf, remove the lift handles and on the bottom
handle mounts, use the two provided partial-threaded custom M6
screws to secure each side of the Enpower and tighten to 0.5 N•m
(4.4 lb•in) or less. The threaded portion of the screw engages with the
bracket, while the unthreaded portion of the screw engages with the
hole in the bracket to prevent vertical movement of the bracket.
*
WARNING!
Risk of injury and equipment damage. Do not skip this
step. Without these screws in place, the Enpower may fall and cause
injury or damage if bumped or shaken.
Use the four filler plates, provided in the lit kit, to cover the screws.
rev.
Modificaton
ECN
Date
Drawing Approved
Material
Hardness
Finish
Description
Phillips truss head machine screw
M6x25
Passivation
Stainless steel 304, A2-70
Customer Code
Customer P/N
& drawing no.
Drawing No.
Article No.
Scale
Size
UNSPECIFIED TOLERANCES
Version
QP Level
Q2
00
All dimensions are in mm
Third angle projection
00 Created
13-Nov-19 Mary He Don Tang
A4
Not ot Scale
6355781
Business Unit
BOC
Important Disclaimer
The technical recommendations contained in this publication are necessarily of a general nature and should not be relied on for specific applications without first
securing competent advice. Whilst Bossard has taken all reasonable steps to ensure the information contained herein is accurate and current, Bossard does not
warrant the accuracy or completeness of the information and does not accept liability for errors or omissions.
Note:
1. Without burr, sharp edges or other disfigurements.
2. The part is RoHS compliance.
3. Comply with thread locking standard IFI 524.
00
Q2
Mary He
Mary He
2019/11/13
6355781
M6xP1.0
Ø6
0 -0.18
13.87-14.55
3.38-3.81
Phillips Drive #3
Nylon blue patch (half circle
90° ~180° ), cover 4-6
threads, 1-2 lead thread
free of locking material
25±0.42
20Ref
730-00296
01 INITIAL RELEASE - ECO-005109
MN
17 FEB 21
M. Nagy
17 FEB 21
780-00568
1
1
Label, Enpower, CT, Field
01
D
C
B
A
B
A
1
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1420 N. McDowell Blvd.
PETALUMA, CA 94954
(707) 763-4784
The information contained in this document is the
proprietary and confidential information of ENPHASE
ENERGY, Inc.. You will not provide, make available
or disclose (or use for any purpose other than that
contemplated by this document) any such information
to any other party without the express, written consent
of ENPHASE ENERGY, Inc.
D
C
SIZE
SHEET OF
REV
DRAWING NO.
2
DWN BY
ENGR
MFG
TITLE
THIRD ANGLE PROJECTION
3D MODEL
REVISIONS
REV
DESCRIPTION
CHKD
DATE
APPROVALS
DATE
B
DO NOT SCALE THIS DRAWING
Scale: 2:1
25.00
8.00
This sensor is part of a
Power Control System.
Do not remove or disable.
Replace with the same type and rating.
7. LABEL MUST BE UL RECOGNIZED (PGDQ2) AND CSA
ACCEPTED AS SUITABLE FOR OUTDOOR USE AT
TEMPERATURES FROM -40°C TO +65°C AND SUITABLE
FOR THE SURFACE TO BE APPLIED (PER UL RECOGNIZED
COMPONENT DIRECTORY). EACH LABEL MUST BE MARKED
WITH VENDOR’S MARK AS DEFINED IN THE CSA LIST OF
ACCEPTED ADHESIVE-TYPE NAMEPLATES. THE SMALLEST
SHIPPING PACKAGE MUST BE MARKED WITH SUPPLIER’S
NAME AND UL DESIGNATION.
1. MATERIAL: 3M 7871 POLYESTER, 3M 350 ADHESIVE
WITH CLEAR OVERLAY ON FRONT.
2. USE UV RESISTANT INK.
3. DIE CUT LABEL AND SHIP IN SHEETS OR ON ROLL.
4. ARTWORK SUPPLIED IN ILLUSTRATOR FORMAT.
5. COLORS: BACKGROUND RED (RGB: 255, 0, 0) TEXT WHITE
6.VENDOR HAS THE AUTHORITY TO MODIFY COLORS
SLIGHTLY TO SUIT AVAILABLE INKS.
Auxiliary Contact Labels
This label can be applied on top of the existing label for the lugs in
Enpower.
Stick Manual Override
label here
01 INITIAL RELEASE - ECO-005109
MN
26 FEB 21
M. Nagy
18 FEB 21
780-00669
1
1
Label, Enpower R1, MOR
01
D
C
B
A
B
A
1
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1420 N. McDowell Blvd.
PETALUMA, CA 94954
(707) 763-4784
The information contained in this document is the
proprietary and confidential information of ENPHASE
ENERGY, Inc.. You will not provide, make available
or disclose (or use for any purpose other than that
contemplated by this document) any such information
to any other party without the express, written consent
of ENPHASE ENERGY, Inc.
D
C
SIZE
SHEET OF
REV
DRAWING NO.
2
DWN BY
ENGR
MFG
TITLE
THIRD ANGLE PROJECTION
3D MODEL
REVISIONS
REV
DESCRIPTION
CHKD
DATE
APPROVALS
DATE
B
DO NOT SCALE THIS DRAWING
Scale: Full
200.00
Manual Override Instructions:
Contact Enphase customer support at (877) 797-4743 and confirm before following instructions below.
Steps for Initiating Manual Override (Tied to Grid)
1. OPEN the breakers for Encharge, Mains, and Auto Transformer in Enpower (The mains breaker could be located inside the main service panel).
Note: No need to open PV combiner and load side breaker inside Enpower.
2. Turn OFF all Encharge units by turning OFF the DC switches on each Encharge base unit.
3. Disable the generator. Turn off generator output breaker inside the generator. Ensure your generator is turned off.
4. Wait for 2 minutes.
5. Remove the sticker from the manual override section of the Enpower. Use a Philips head screwdriver to remove the screw on the plastic cover.
Then remove the plastic cover to make the small manual override toggle visible.
6. Turn the toggle to the
left
to manually CLOSE the MID relay.
7. CLOSE the mains breaker.
The Enpower system is now in manual override mode and grid tied.
Steps for Exiting Manual Override:
1. OPEN the breakers for Encharge, Mains, and Auto Transformer in Enpower.
2. Turn OFF all Encharge units by turning OFF their DC switches.
3. Wait for 2 minutes.
4. Turn the manual override toggle to the
right
to manually OPEN the MID relay.
5. CLOSE all the breakers in sequence:
a. NFT breaker inside Enpower
b. Mains breaker (In Enpower or main panel)
c. Encharge breaker inside Enpower
6. Turn ON all Encharge units by turning ON their DC switches.
The Enpower system is now no longer in manual override mode and is fully fuctional.
7. LABEL MUST BE UL RECOGNIZED (PGDQ2) AND CSA
ACCEPTED AS SUITABLE FOR OUTDOOR USE AT
TEMPERATURES FROM -40°C TO +65°C AND SUITABLE
FOR THE SURFACE TO BE APPLIED (PER UL RECOGNIZED
COMPONENT DIRECTORY). EACH LABEL MUST BE MARKED
WITH VENDOR’S MARK AS DEFINED IN THE CSA LIST OF
ACCEPTED ADHESIVE-TYPE NAMEPLATES. THE SMALLEST
SHIPPING PACKAGE MUST BE MARKED WITH SUPPLIER’S
NAME AND UL DESIGNATION.
1. MATERIAL: 3M 7871 POLYESTER, 3M 350 ADHESIVE
WITH CLEAR OVERLAY ON FRONT.
2. USE UV RESISTANT INK.
3. DIE CUT LABEL AND SHIP IN SHEETS OR ON ROLL.
4. ARTWORK SUPPLIED IN ILLUSTRATOR FORMAT.
5. COLORS: BACKGROUND WHITE, BLACK C
6.VENDOR HAS THE AUTHORITY TO MODIFY COLORS
SLIGHTLY TO SUIT AVAILABLE INKS.
100.00
Scan QR code to view
instruction videos
Label Sample
Label Sample
Stick PCS label here
PCS Label
Apply the PCS label on the deadfront. Record the maximum operating
amps value on the label. This value indicates the maximum current
5
7
8
9
6
Stick CT label
for PCS here
Stick CT label
for PCS here
Label Sample