IQ 6 / IQ 6+ Micro Installation and Operation
© 2017 Enphase Energy Inc. All rights reserved.
141-00034-01
33
SA10: Low/High Frequency Ride Through (L/H FRT) and Must Trip Settings
Units
Ride Through
Must Trip
Max
Min
Max
Min
High frequency 2-time
s
NA
NA
0.5
0.1
High frequency 2-magnitude
Hz
NA
NA
65
60.3
High frequency 1-time
s
599.8
0.8
600
0.16
High frequency 1-magnitude
Hz
65
60.1
65
60.1
Low frequency 1-time
s
599.8
0.8
600
0.16
Low frequency 1-magnitude
Hz
59.9
57
59.9
57
Low frequency 2-time
s
NA
NA
0.5
0.1
Low frequency 2-magnitude
Hz
NA
NA
59.9
50
SA11: Ramp Rate (RR) and Soft Start (SS)
Units
Adjustment Range
Tolerance
Max
Min
Ramp-up rate
%Irated/s
100
1
+/- 3% I rated
Soft start ramp rate
%Irated/s
100
0.11
+/- 3% I rated
SA12: Specified Power Factor (SPF), aka (INV3)
Units
Adjustment Range
Max
Min
Inductive, under excited, power factor
VAr/W
-0.7
-1.0
Capacitive, overexcited, power factor
VAr/W
1.0
0.7
SA13: Volt/VAr Mode (VV)
Units
Adjustment Range
Max
Min
Minimum AC EPS voltage range
P.U.
0.80
1.0
Maximum EUT input voltage
P.U.
1.20
1.0
AC power
W
280
0
Reactive power absorption (inductive, under excited)
VAr
200
50
Reactive power production (capacitive, overexcited)
VAr
200
50
Slope
VAr/V
50
0
Deadband
V
48
4.8