SA14: Frequency-Watt (FW)
Units
Adjustment Range
Max
Min
AC frequency with function enabled
Hz
57
65
High end frequency droop settings
Hz
62
60.1
Slope of frequency droop
%Prated/Hz
200
20
SA15: Volt-Watt (VW)
Units
Adjustment Range
Max
Min
Adjustment range of the start of the curtailment function
V
130.0
121.0
Adjustment range of the stop of the curtailment function
V
138.0
123.0
Slope of voltage curtailment
%Prated/V
83