IQ 7 / IQ 7+ / IQ 7X / IQ 7A Micro Installation and Operation
© 2020 Enphase Energy Inc. All rights reserved.
141-00043-03
37
IQ7A-72-2-US Microinverter Specifications
IQ7A-72-2-US Microinverter
Parameters
Topic
Unit
Min
Typical
Max
DC Parameters
Commonly used module pairings
10
W
295 W - 460+ W
Peak power tracking voltage
V
38
43
Operating range
V
18
58
Maximum DC input voltage
V
58
Minimum / maximum start voltage
V
30
58
Maximum DC input short circuit current (module Isc)
A
15
Overvoltage class DC port
II
DC Port backfeed under single fault
A
0
PV array configuration
1x1 ungrounded array; No additional DC side protection
required; AC side protection requires max 20A per branch circuit
AC Parameters
Maximum continuous AC output power (-40 to +60
C)
VA
349 VA @ 240 VAC
290 VA @ 208 VAC
Peak output power
VA
366 VA @ 240 VAC
295 VA @ 208 VAC
Power factor (adjustable)
0.85 leading
0.85 lagging
Nominal AC output voltage range
11
240 VAC (single phase)
208 VAC (single phase)
Vrms
Vrms
211
183
264
229
Nominal output current
240 VAC (single phase)
208 VAC (single phase)
Arms
Arms
1.45
1.39
Nominal frequency
Hz
60
Extended frequency range
Hz
47
68
Maximum AC output over current protection device
A
20
AC short circuit fault current over 3 cycles
A rms for over 3
cycles
5.8 Arms
High AC voltage trip limit accuracy
%
1.0
Low AC voltage trip limit accuracy
%
1.0
Frequency trip limit accuracy
%
±0.1
Trip time accuracy
milliseconds
±0.1% or 2 cycles
Overvoltage class AC port
III
AC port backfeed under single fault
A
0
Power factor setting
1.0
10
No enforced DC/AC ratio. See the compatibility calculator at
enphase.com/en-us/support/module-compatibility
11
Nominal Voltage Range can be extended if required by the utility.