M250 (M250-60-2LL) Safety
 

Important Safety Information

This document contains important instructions to use during installation of the Enphase M250 Microinverter™. To reduce 

the risk of electrical shock, and to ensure the safe installation and operation of the Enphase Microinverter, follow these in-

structions. The following safety symbols and information indicate dangerous conditions and important safety instructions.

Product Labels

WARNING:

 Hot surface.

DANGER

: Risk of electrical shock.

Refer to product instructions.

Safety Instructions

DANGER

: Before installing or using the Enphase Micro-

inverter, read all instructions and cautionary markings in 

the technical description, on the Enphase Microinverter 

System, and on the photovoltaic (PV) equipment.

DANGER

: Do not use Enphase equipment in a manner 

not specified by the manufacturer. Doing so may cause 

death or injury to persons, or damage to equipment.

DANGER

: Risk of Electrical Shock. Be aware that instal-

lation of this equipment includes risk of electric shock. 

Do not install the AC junction box without first removing 

AC power from the Enphase System. 

DANGER

: The Engage Cable terminator cap must not 

be installed while power is connected.

DANGER

: Electric shock hazard. The DC conductors 

of this photovoltaic system are ungrounded and may be 

energized.

WARNING

: Always de-energize the AC branch circuit 

before servicing. Never disconnect the DC connec-

tors under load. Disconnect DC connections first, then 

disconnect AC connections.  

WARNING

: The body of the Enphase Microinverter is 

the heat sink. Under normal operating conditions, the 

temperature is 15°C above ambient, but under extreme 

conditions the microinverter can reach a temperature of 

80°C. To reduce risk of burns, use caution when work-

ing with microinverters.

WARNING

: The M250 may be paired only with a 60-cell 

PV module. The PV module DC conductors must be la-

beled “PV Wire” or “PV Cable” to be compliant with NEC 

690.35(D) for Ungrounded PV Power Systems.

WARNING

: If the AC cable on the microinverter is dam-

aged, do not install the unit. 

WARNING

: You must match the DC operating voltage 

range of the PV module with the allowable input voltage 

range of the Enphase Microinverter: 16-48V.

WARNING

: The maximum open circuit voltage of the PV 

module must not exceed the specified maximum input 

voltage of the Enphase Microinverter: 48V DC.

WARNING

: The M250 has field-adjustable voltage and 

frequency trip points that you may need to set, depend-

ing upon local requirements. Only an authorized installer 

with the permission and following requirements of the 

local electrical authorities should make adjustments. 

WARNING

: Only use electrical system components ap-

proved for wet locations.

WARNING

: Only qualified personnel should trouble-

shoot, install, or replace Enphase Microinverters or the 

Engage Cable and Accessories.

WARNING

: Make sure protective sealing caps have 

been installed on all unused AC connectors. Unused AC 

connectors are live when the system is energized by the 

grid. Sealing caps may not be reused.

WARNING

: Ensure that all AC and DC wiring is correct 

and  that none of the AC or DC wires are pinched or 

damaged. Ensure that all AC junction boxes are properly 

closed. 

Safety and Advisory Symbols

DANGER

! This indicates a hazardous situation, which if 

not avoided, will result in death or serious injury.

WARNING

! This indicates a situation where failure to 

follow instructions may be a safety hazard or cause 

equipment malfunction. Use extreme caution and follow 

instructions carefully.

WARNING

! This indicates a situation where failure to 

follow instructions may result in burn injury. 

NOTE

: This indicates information particularly impor-

tant for optimal system operation. Follow instructions 

closely.

  M 2 5 0   S A F E T Y

®

Summary of Contents for M250

Page 1: ...rters WARNING The M250 may be paired only with a 60 cell PV module The PV module DC conductors must be la beled PV Wire or PV Cable to be compliant with NEC 690 35 D for Ungrounded PV Power Systems WARNING If the AC cable on the microinverter is dam aged do not install the unit WARNING You must match the DC operating voltage range of the PV module with the allowable input voltage range of the Enph...

Page 2: ...s destroyed and the terminator cap cannot be used again If the latching mechanism is defective the terminator must not be used The latching mechanism must not be circumvented or manipulated WARNING When stripping the sheath from the Engage Cable make sure that the conductors are not damaged If the exposed wires are damaged the system may not function properly WARNING Perform all electrical install...

Page 3: ...it to Enphase Click Add New System at www enlighten enphaseenergy com Use this map to build the virtual array in Enlighten s Array Builder DOCUMENT NUMBER ENPHASEENERGY COM INSTALLATION MAP REVISION 140 00003 04 A B C D E F G H J K L M 1 2 3 4 5 6 7 To Sheet ________ To Sheet ________ To Sheet ________ To Sheet ________ Envoy Serial Label ...

Page 4: ...nstalled racking for the AC branch circuit b Install an appropriately rated off the shelf junction box at a suitable location on the racking See notes in Step Details on back Warning Do not remove power from the Envoy if the LCD displays Upgrading Do Not Unplug AC power cord broadband router Envoy Ethernet cable Check the drop connector labels to be sure that you have the right cable You must use ...

Page 5: ...ng caps Listen for two clicks as the connectors engage See notes in Step Details on back Do not use shipping caps to cover unused connectors The shipping cap does not provide an adequate environmental seal b Mount the microinverter under the PV mod ule away from rain and sun Do not mount the microinverter in a position that allows long term exposure to direct sunlight or in a vertical orienta tion...

Page 6: ... 8 Complete the Installation Map Build the map manually or use the Array Gun tool to map the system For more information go to http enphase com products arraygun To manually build the map peel the removable se rial number label from each microinverter and affix it to the respective location on the map included with this guide serial number labels b Check that all terminator parts are present Never...

Page 7: ... the top of the microinverter NOTE Torque the microinverter fasteners to the values shown Do not over torque 1 4 mounting hardware 5 N m 45 50 in lbs 5 16 mounting hardware 9 N m 80 85 in lbs Using a power screwdriver is not recommended due to the risk of thread galling NOTE The AC output neutral is not bonded to ground inside the microinverter WARNING Install sealing caps on all unused AC connect...

Reviews: