16
RAK75 / © Ensto 2018
6.2 Commissioning
•
Start the thermostat with the power switch.
•
The
START UP
menu opens. The
START UP
menu opens only, when the thermostat is switched on for
the first time or when the factory settings are reset by using the
RESET / FACT SET
function.
•
Set and save the settings that are displayed alternately in the
START UP
menu.
•
After a possible power failure day and time must be set, the other settings will be retained.
LANGUAGE
Select the required language by scrolling the options using the
or
button.
Save the selection with
Default: ENGLISH
Options:
SWEDISH, DEUTCH, NORSK, SUOMI, РУССКИЙ
DATE/TIME
The date and time must be set in order for the program functions to work correctly.
First set the date: dd.mm.yyyy
Then set the time: hh:mm
The value to be set blinks.
Increase or decrease the blinking value using the
or
button.
Save the setting with
OPERATION MODE
Select the required operation mode by scrolling the options using the
or
button.
Save the selection with
Note! After leaving the
START UP
menu the operation mode can be changed only by resetting the factory
settings.
EXIT
When you have made all the commissioning settings, select
EXIT
.
Leave the
START UP
menu by selecting
YES
.
The thermostat goes to basic display mode.
6.3 Basic Display Mode
In the basic display mode the display shows the operation mode, alternatingly the set point and the current
value as well as if the system is switched on or off. The thermostat returns into basic display mode and the
display dims 30 seconds after a button has been pressed.
* The current value is only shown for the sensors that are installed and activated.
Operation mode
Program
Set point
ON or OFF
Heading
Temperature at
sensor A *
ON or OFF
Temperature at
sensor B *
Humidity at
sensor C *
HEAT
PERSONAL
TMP: +20.0
IDLE
SENSOR
RM: 20.5
IDLE