393930-2 Rev 0: 01.04.2020
10 |
P a g e
,
,
4.1
User selection sub-menu
The unit has a digital input which can trigger a user- configurable function, i.
e. an increased fan speed when guests are coming. The input overrides the
normal operation
Select program: None, Fan boost, Supply air, Extract air, Extern alarm. Default
None
Menu only visible if a duration after activation can be set. Else function is
active when digital input is active.
Range Off: Until input is released; 15 min to 8 hours Menu visible for some
programs.
Set the fan speed to use when digital input is active
Range Off, MIN, NORM, MAX
4.2
Alarm handling menus
Sub-menu with warnings and critical alarms for the air handling unit.
Critical alarms will stop the unit. The unit may continue operation with a
warning.
If the alarm icon is red
it is a critical alarm and the air handling unit will
stop.
Touch to open a more detailed description
If the alarm icon is yellow
it is a warning and the air handling unit may
continue to operate
Touch to open a more detailed description
If the alarm icon is grey, , it is an inactive warning or critical alarm. The
alarm may have to be acknowledged to start the unit again.
Touch to open a more detailed description
Detailed description of a warning or critical alarm
Date/time the alarm came active
Touch Clear alarm to clear the alarm. If the alarm number starts with small
letters, c/w, the alarm can be cleared Alarm number, severity and description
Trouble shooting information for the alarm/warning
Summary of Contents for AHU 200B
Page 1: ...User manual and Installation Guide InoVent AHU 200 700 ...
Page 2: ...393930 2 Rev 0 01 04 2020 2 P a g e ...
Page 31: ...393930 2 Rev 0 01 04 2020 31 P a g e ...
Page 41: ...393930 2 Rev 0 01 04 2020 41 P a g e ...
Page 72: ...393930 2 Rev 0 01 04 2020 72 P a g e Ensy AS Mohagasvingen 1 N 2770 JAREN http www ensy no ...