393930-2 Rev 0: 01.04.2020
24 |
P a g e
4.8.5
Room temperature control
Settings for the room temperature control
The controlling sensor is either the extract air or supply air temperature
sensor
Range Extract air, Supply air; default Extract air Select reaction speed to a
temperature change. Range: Slow, Normal, Fast, User.
Default Normal
User defined neutral zone (2 = ±1). Used to extend the passive operation
range around the setpoint
Range 0°C to 10°C. Default 2°C
Enable low room temperature action and alarm. Inlet fan speed may be
reduced step by step to avoid sub-cooling of the house.
Range Off, 1°C to 20°C. Default 5°C
4.8.6
Supply temperature control
Inlet temperature controller gain Range 0%/° to 30 %/°
Default 7%/°
Supply temperature controller integration time. If set to zero, only P-control
will be active.
Range 0 sec to 600 sec; default 120 sec
Inlet temperature controller neutral zone (2 = ± 1°C) Range 0°C to 10°C
Default 0.5°C
Summary of Contents for AHU 200B
Page 1: ...User manual and Installation Guide InoVent AHU 200 700 ...
Page 2: ...393930 2 Rev 0 01 04 2020 2 P a g e ...
Page 31: ...393930 2 Rev 0 01 04 2020 31 P a g e ...
Page 41: ...393930 2 Rev 0 01 04 2020 41 P a g e ...
Page 72: ...393930 2 Rev 0 01 04 2020 72 P a g e Ensy AS Mohagasvingen 1 N 2770 JAREN http www ensy no ...