2.3 Placement under concrete ceiling
If the unit is to be mounted directly into concrete ceiling where there may be uneven or not level than it
may be easiest to use expansion bolts fastened into the ceiling. That way, you can adjust with the nuts so
that the unit is in level.
If so, then use the suspension brackets as jigs
for the bolts so that the distance between
brackets will be correct.
Use correct drill for use for the M10 mm
expansion bolts.
Make sure the bolt is turned so hard that it
can not loosen. The bolts are available in
different lengths so select someone suitable
for this purpose. Lift the unit into position.
Use a rubber cushioning, 4-6 mm thick,
between washers and mounting brackets.
Then adjust with the nuts so that the unit is in
level.