Multi-Function Control ETMFC610
http://www.entecene.co.kr
184
EN
HANCED
TEC
HNOLOGY
8.1. Fault Indication
Place the curser on “FAULT INDICATION” in GROUP# menu, press [ENT] button to move into
this menu. This menu sets the fault indication element that operate when the fault indication control
type(FITYPE) is set.
8.1.1. FI Type
This menu sets the detection type of fault indication(FI). According to this setting, the fault
indication detection method is applied differently.
GROUP # / FAULT INDICTION / FI TYPE / Type Select
Range
IV, I
Default
IV
Step
~
Select the type of FI(fault indicator) detection.
IV :
If dead line state after experiencing a fault current, FI is
detected.
When using the Autop Sectionalizer (SEC) function in the Loop
Control menu, the FI Type setting must be "IV" for correct Auto
Sectionalizer operation.
I :
If fault current maintains during the fault delay time(Type I
delay), FI is detected.
*. NOTE )
See
“8.1.3.
FI Setting Time”
for details on FI Types.
[FAULT INDICATION]
>1.FI TYPE
>
2.FI PICKUP CURRENT
3.FI SETTING TIME
4.INRUSH RESTRAINT
[FI TYPE]
>Type Select: IV
[IV/I]