Multi-Function Control ETMFC610
http://www.entecene.co.kr
18
EN
HANCED
TEC
HNOLOGY
Frequency
Under Frequency 1,2
Function……………………………………….. DISABLE/ENABLE
Pickup Level …………………………………... 45.00 to 65.00 in steps of 0.01
㎐
Time Delay……………………………………..0.00 to 600.00s in steps of 0.01s
Reset Time………………………….…………. 0.00 to 600.00s in steps of 0.01s
Minimum Normal Voltage……………………...0.00 to 1.40xVT in steps of 0.01xVT
Minimum Normal Current………………………OFF, 1 to 630A in steps of 1A
Over Frequency 1,2
Function……………………………………….. DISABLE/ENABLE
Pickup Level …………………………………... 40.00 to 65.00 in steps of 0.01
㎐
Time Delay……………………………………..0.00 to 600.00s in steps of 0.01s
Reset Time………………………….…………. 0.00 to 600.00s in steps of 0.01s
Minimum Normal Voltage……………………...0.00 to 1.40xVT in steps of 0.01xVT
Minimum Normal Current………………………OFF, 1 to 630A in steps of 1A
Frequency Decay
Function………………………………………..DISABLE/ENABLE
Pickup Level(Hz/sec) …………………………0.01 to 5.00 in steps of 0.01
㎐
/sec
Time Delay……………………………………..0.00 to 600.00s in steps of 0.01s
Reset Time………………………….……….….0.00 to 600.00s in steps of 0.01s
Minimum Normal Frequency…..……………...45.00 to 65.00 in steps of 0.01
㎐
Minimum Normal Voltage……………………...0.00 to 1.40xVT in steps of 0.01xVT
Minimum Normal Current………………………OFF, 1 to 630A in steps of 1A
Active Type………….…………………………INCREASE/DECREASE/ABSOLUTE
Level Accuracy .......................................................... at VT ± 0.02
㎐
, at CVD ± 0.05
㎐
Dropout Level ........................................................... at VT 0.02
㎐
when Under Frequency
at CVD 0.05
㎐
when Under Frequency
at VT Pickup - 0.02
㎐
when Over Frequency
at CVD Pickup -0.05
㎐
when Over Frequency
Timing Accuracy ....................................................... Max. 50
㎳
at 0
㎳
trip time delay
5% of setting time or ± 20
㎳