GROUP # / MONITORING / BROKEN CONDUCT / Min. I
Range
0(OFF), 1~630A
Default
60
Step
1A
Enter the minimum value of current required to allow the broken
conduct element to operate.
Positive sequence current is less than setting value, element will not
operate.
GROUP # / MONITORING / BROKEN CONDUCT / Min. I
Range
0(OFF), 10~1600
Default
500
Step
1A
Enter the maximum value of current required to allow the broken
conduct element to operate.
Positive sequence current is greater than setting value, element will not
operate.
8.5.2. Voltage (27/59/64N/47P)
Place the curser on “VOLTAGE” in MONITORING menu, press [ENT] button to move into this
menu. In this menu, undervoltage, overvoltage and neutral elements will be described. And the
voltage menu is composed with 6 sub-menus as follows:
8.5.2.1. Undervoltage (27)
In case that nominal voltage is kept below a certain voltage for a certain time, two under voltage
elements make an alarm operation.
The under voltage element are set in GROUP setting. It is available to select a number of phase to
be checked for undervoltage function.
[BROKEN CONDUCT]
Function: DISABLE
Pickup(I2/I1): 5
Time Delay: 4.00
>Min.I: 60
>
Max.I: 500
[0(OFF), 1~630:1 A]
[BROKEN CONDUCT]
Function: DISABLE
Pickup(I2/I1): 5
Time Delay: 4.00
>
Min.I: 60
>Max.I: 500
[0(OFF),10~1600:1 A]
[VOLTAGE]
>1.UNDER VOLT1
2.UNDER VOLT2
3.OVER VOLT1
4.OVER VOLT2
5.NEUTRAL OVERVOLT1
6.NEUTRAL OVERVOLT2