Multi-Function Control ETMFC610
http://www.entecene.co.kr
291
EN
HANCED
TEC
HNOLOGY
GROUP # / REC MONITORING LOSER / DEMAND / PHASE
/
Time Delay
Range
0.00~600.00
Default
10.00
Step
0.01sec
Set the time delay of the phase demand current element
GROUP # / MONITORING / DEMAND / PHASE
/
Demand Type
Range
THERMAL, BLOCK
Default
THERMAL
Step
~
Set the type of arithmetic operation for the phase demand current
element.
GROUP # / MONITORING / DEMAND / PHASE
/
Thermal Interval
Range
5, 10, 15, 20, 30, 60 min
Default
15
Step
~
Set the interval of the phase demand current element when thermal type
is selected for arithmetic operation.
GROUP # / MONITORING / DEMAND / PHASE
/
Block Interval
Range
5, 10, 15, 20, 30, 60 min
Default
15
Step
~
Set the interval of the phase demand current element when block type
is selected for arithmetic operation.
8.5.5.2. Ground Demand Current (49G)
Ground demand current element settings process is similar method to the phase demand current
element.
8.5.5.3. Negative Sequence Demand Current (49Q)
Negative sequence demand current element settings process is similar method to the phase demand
current element.
[PHASE]
Pickup: 500
>Time Delay: 10.00
Demand Type:THERMAL
Thermal Interval:15
Block Interval: 15
[0.00~600.00:0.01s]
[PHASE]
Pickup: 500
Time Delay: 10.00
>Demand Type:THERMAL
Thermal Interval:15
Block Interval: 15
[THERMAL/BLOCK]
[PHASE]
Pickup: 500
Time Delay: 10.00
Demand Type:THERMAL
>Thermal Interval:15
Block Interval: 15
[5/10/15/20/30/60m]
[PHASE]
Pickup: 500
Time Delay: 10.00
Demand Type:THERMAL
Thermal Interval:15
>Block Interval: 15
[5/10/15/20/30/60m]