Multi-Function Control ETMFC610
http://www.entecene.co.kr
21
EN
HANCED
TEC
HNOLOGY
Open Phase
Function..................................................................... DISABLE/ENABLE
On Level .................................................................... 0.10 to 1.40xVT in steps of 0.01xVT
Off Level ................................................................... 0.10 to 1.40xVT in steps of 0.01xVT
Time Delay ................................................................ 0.00 to 600.00s in steps of 0.01s
Level Accuracy .......................................................... 5%
Timing Accuracy ....................................................... ± 5% of setting time or ± 20msec
Live Line Block
Function..................................................................... DISABLE/ENABLE
Live Level ................................................................. 0.10 to 1.40xVT in steps of 0.01xVT
Live Line Check Source ............................................ VS/VL/VS&VL
Time Delay ................................................................ 0.00 to 600.00s in steps of 0.01s
Level Accuracy .......................................................... 5%
Timing Accuracy ....................................................... ± 5% of setting time or ± 20msec
Fault Locator
Function..................................................................... DISABLE/ENABLE
Total Length of Feeder .............................................. 0.1 to 99.9 of 0.1km
Real impedance of the feeder positive seq. ............... 0.01 to 99.99 of 0.01ohms
Imaginary impedance of the feeder positive seq. ...... 0.01 to 99.99 of 0.01ohms
Real impedance of the feeder zero seq. ..................... 0.01 to 99.99 of 0.01ohms
Imaginary impedance of the feeder zero seq ............. 0.01 to 99.99 of 0.01ohms
Load Current Alarm
Function..................................................................... DISABLE/ENABLE
Phase/Ground/Neg Seq’ Pickup Level ...................... OFF, 10 to 1600A in steps of 1A
Phase/Ground/Neg Seq’ Time Delay ........................ 0.00 to 600.00s in steps 0.01s
Level Accuracy .......................................................... ± 5%
Timing Accuracy ....................................................... ± 5% of setting time or ± 20msec