Multi-Function Control ETMFC610
http://www.entecene.co.kr
301
EN
HANCED
TEC
HNOLOGY
The fault locator settings are as follows;
GROUP # / MONITORING / FAULT LOCATOR / Function
Range
DISABLE, ENABLE
Default
DISABLE
Step
~
It decides whether to use Fault locator.
GROUP # / MONITORING / FAULT LOCATOR / Feeder Length
Range
1.0 ~ 99.9 km
Default
5.0
Step
0.1 km
Enter the total length of the feeder in kilometers
GROUP # / MONITORING / FAULT LOCATOR / Z1 (Real)
Range
0.01~99.9 9 ohm
Default
1.00
Step
0.01ohm
Enter the total real components of the feeder positive sequence
impedance, in actual ohms.
GROUP # / MONITORING / FAULT LOCATOR / Z1 (Imag)
Range
0.01~99.9 9 ohm
Default
1.00
Step
0.01ohm
Enter the total imaginary components of the feeder positive sequence
impedance, in actual ohms.
GROUP # / MONITORING / FAULT LOCATOR / Z0 (Real)
Range
0.01~99.9 9 ohm
Default
1.00
Step
0.01ohm
Enter the total real components of the feeder zero sequence impedance,
in actual ohms.
[FAULT LOCATOR]
>Function: DISABLE
Feeder Length: 5.0
Z1 (Real): 1.00
Z1 (Imag): 1.00
Z0 (Real): 1.00
Z0 (Imag): 1.00
[DISABLE/ENABLE]
[FAULT LOCATOR]
Function: DISABLE
>Feeder Length: 5.0
Z1 (Real): 1.00
Z1 (Imag): 1.00
Z0 (Real): 1.00
Z0 (Imag): 1.00
[1.0~99.9:0.1km]
[FAULT LOCATOR]
Function: DISABLE
Feeder Length: 5.0
>Z1 (Real): 1.00
Z1 (Imag): 1.00
Z0 (Real): 1.00
Z0 (Imag): 1.00
[0.01~99.99:0.01ohm]
[FAULT LOCATOR]
Function: DISABLE
Feeder Length: 0.0
Z1 (Real): 1.00
Z1 (Imag): 1.00
Z0 (Real): 1.00
Z0 (Imag): 1.00
[0.01~99.99:0.01ohm]
[FAULT LOCATOR]
Function: DISABLE
Feeder Length: 0.0
Z1 (Real): 1.00
Z1 (Imag): 1.00
Z0 (Real): 1.00
Z0 (Imag): 1.00
[0.01~99.99:0.01ohm]