Battery Automatic Load Test
Test Period ................................................................. OFF, 1 to 720 hours in steps of 1hour
Battery Management
Function..................................................................... DISABLE/ENABLE
Charge Time .............................................................. 60 to 6,000 min. in steps of 1 min.
Discharge Time ......................................................... 60 to 6,000 min. in steps of 1 min.
Alarm Pickup Level .................................................. 0.00 to 100.00% in steps of 0.01%
Reset Battery Capacity .............................................. 0.00 to 100.00% in steps of 0.01%
Power Quality Monitoring(PQM)
Function..................................................................... DISABLE/ENABLE
Interrupt
Pickup Level …………………………………. OFF, 0.10 to 0.49xVT in steps of 0.01xVT
Time Delay……………………………………0.5 to 10.0cycle in steps of 0.5 cycle
Sag
Pickup Level …………………………………. OFF, 0.50 to 0.99xVT in steps of 0.01xVT
Time Delay……………………………………0.5 to 10.0cycle in steps of 0.5 cycle
Swell
Pickup Level …………………………………. OFF, 1.01 to 1.50xVT in steps of 0.01xVT
Time Delay……………………………………0.5 to 10.0cycle in steps of 0.5 cycle
Harmonics
Voltage Total Harmonics Pickup Level………OFF, 0.5 to 100.0% in steps of 0.1%
Voltage Total Harmonics Time Delay………..0.00 to 600.00sec in steps of 0.01sec
Current Total Harmonics Pickup Level………OFF, 0.5 to 100.0% in steps of 0.1%
Current Total Harmonics Delay Time…….…..0.00 to 600.00sec in steps of 0.01sec
Current Unbalance
Pickup Level ………………………………….OFF, 0.5 to 100.0% in steps of 0.1%
Time Delay……………………………………0.5 to 10.0cycle in steps of 0.5 cycle
Voltage Unbalance
Pickup Level ………………………………….OFF, 0.5 to 100.0% in steps of 0.1%
Time Delay……………………………………0.5 to 10.0cycle in steps of 0.5 cycle
Under Voltage
Pickup Level ………………………………….0.10 to 1.40xVT in steps of 0.01xVT
Time Delay……………………………………0.00 to 600.00sec in steps of 0.01sec