36
Entek IRD 6666 and 6667 Protection Monitors
Configuration
9.
To set the second source in ALM1MAP, select ALMSRC2.
The second source for ALM1MAP is the channel 2 Danger alarm.
10. Select ALM1 2 (alarm map 1, source 2) and set it to DANGER.
11. Select SRC NUM and set it to 2 for channel 2.
12. Since this is the last source in ALM1MAP, select COMBINE and set it to END.
You have now set ALM1MAP to channel 1 Alert alarm AND channel 2 Danger alarm.
You have now set the first equation:
relay 2 = channel 1 Alert AND channel 2 Danger
You now need to set ALM2MAP.
13. Select EXIT twice to return to the ALM2MAP option.
To set ALM2MAP
1.
Select ALM2MAP.
2.
To set the first source in ALM2MAP, select ALMSRC1. Note that this menu might
contain additional source options.
The first source for ALM2MAP is a channel 2 Alert alarm.