Installation Requirements and Specifications
2-1
2
Installation Requirements and Specifications
This chapter describes the following:
•
Site guidelines that must be met before installing a 5C105 into a rack or cabinet
•
5C105 configuration guidelines
•
Operating specifications for the 5C105 enclosure and power supply module
2.1
SITE GUIDELINES
The following guidelines must be followed when a site is selected for the 5C105. If the guidelines
are not followed, unsatisfactory network performance may result.
•
In order to allow proper cooling within the rack, there must be 3 inches of clearance above the
unit and 2 inches of clearance on either side of the unit.
•
If the 5C105 is to be rack mounted, care must be taken to ensure that the rack used will support
the unit and that the rack remains stable with the 5C105 installed.
•
The 5C105 ac power supplies require a standard three-pronged power receptacle that is located
within 6 feet of the site.
•
The temperature of the location must be maintained between 5° and 40°C (41° to 104°F).
Temperature changes of greater than 10°C (18°F) per hour must not occur.
ELECTRICAL HAZARD: Only qualified personnel should install or service this unit.
NOTE: Read the Release Notes shipped with the chassis to check for any exceptions to
the supported features and operation documented in this guide.