MENUS :
As above example, relay will switch on at 18:00 PM for all weekdays via
time function.
Sunset settings are similar with sunrise settings.
As above example, C1 relay will switch on 2 hours 30 minutes before the
sunrise time for all weekdays.
1.5.3)
( ) In this menu, sunset function is selected
As above example, C1 relay will switch off 1 hour 50 minutes before the
sunset time for all weekdays.
NOTE :
Device calculates the sunrise and sunset times automatically
according to the summer/winter time and coordinate information which
are set by user.
Go to previous menu.
Go to next menu.
Scrolling between menus or decrease related value.
Relay position is change manually if press for 3 sec. in
start menu.
Scrolling between menus or increase related value.
ESC button
SET button
DOWN button
UP button
:
:
:
:
DTR-10t, which has a real time clock, is an electronic timer that calculate
the sunset and sunrise periods automatically. It designed for controlling
the devices which are connected to its contacts according to sunset,
sunrise and the time periods which are proggrammed by the user.
1 ) PROGRAM ( ) :
In this menu, program settings can be done.
Only one function ON or
OFF can be assigned to each program. Only one of TIME, SUNRISE
or SUNSET functions can be selected (assigned) for this function. The
day and/or days of active can be selected separately for this program.
2 different program assigned in order to make eaiser the using of device
by switch it ON at sunset time and switch OFF at sunrise time. These
programs which are assigned as default, can be deleted or changed by
the user.
Related steps are mentioned as below:
If 0:00 is set, relay will be controlled at sunrise time. By this
feature, devices which are connected to the relays, can be
controlled after or before the sunrise time.
Relay can be controlled before or after the sunrise time according to the
entered time information. This value can be set as hour or minute.
(Max: +9:59, Min: -9:59)
1.5.2)
( ) In this menu, sunrise function is enabled however
sunrise time is not set.
The output loads connected to the C1 relay do not function if
auxiliary supply is off. Even relay status can be mentioned as on
( ), but auxiliary supply is a must for the functionality.
If the auxiliary supply does not exist, device passes to sleep mode
and display disappears. However, real time clock and related functions
continue to operate. If 4 buttons are pressed at the same time, main menu
displays and so user can see or change all settings.
1.1)
Program selection
( ) :
Device has 15 different
programs. User can assign 1 function to any program between P01-P15.
Relay can be selected via one program and also relay can only be set as
switch on or switch off.
For instance; If the status of C1 relay is set as ON (switch on), 1 program
is used.
In order to switch off the relay which was set as ON before, another
program must be used (Such as 2nd program).
Star sign which exists after the program number ( ) represents
that the program is assigned.
1.5.1)
( )
Selected relay can be switched on/off at defined
time period.
1
Safety Precautions
If below precautions are not properly observed and carried out, it can
cause to physical accident or damage to the device and installation.
Disconnect power before working on the device.
When device is connected to the network, do not remove the front panel.
Do not clean the device with solvent or similar items. Only clean with
dried cloth.
Verify correct terminal connections before operate the device.
Connect the device to the electrical panel.
Electrical equipment should be serviced only by your competent seller.
No responsibility is assured by the manufacturer or any of its
subsidiaries for any consequences rising out of the use of this
material.
C2:
C1:
00
02
04
06
08
10
12
14
16
22
20
18
24
MO
WE
FR SA SU
TH
TU
ESC
SET
Day
1.2) Enter / Delete settings ( / ) :
is used to set
a new program or to change the existing program.
is used to delete the existing program.
1.3)
Shows that C1 relay assigned to which program.
The relay, which is switched on via any program, can not be switched off
by deleting the related program. We can switch off the relay in two ways:
a)
Switch off (OFF) the relay manually. (Check the LOCK section)
b)
Enter the switch off time (OFF) for any relay. Delete the program after
the relay switched it off (OFF).
1.5)
Function selection ( / / ) :
Function
selection is done in this menu. 1 function can be selected for each program.
3 functions exist: Time, sunset and sunrise.
1.4) ON/OFF selection ( / ) :
In this menu, it is selected
that whether selected C1 relay will switch on or switch off.
C1
C1
When programmed in program menu, C1 relay is
programmed as ON. Relay contact position looks like on the figure
at left side. Relay contacts seem at monitor as .
When programmed in program menu, C1 relay is
programmed as ON. Relay contact position looks like on the
figure at left side. Relay contacts seem at monitor as .
ASTRONOMIC RELAY
(DTR-10t)
CR-2032 reserve battery should only be changed by authorized service.
For long time reserve, battery CR-2032 is used. The shelf life of this
battery is 5 years, if the device is continously voltage supplied. If the
device is not continously voltage supplied and waited in the shelf, the life
of the battery is 2-3 years (changes according to humidity of the shelf).
There are two reserves in the device. Programmed data is protected
by these reserve against power failure.
If power fails for 6-10 hours, programmed data is protected by super
capacitor and device continues to its operation. During this time battery
(CR2032) is not used; so battery life extends.
For short time, super capacitor is used:
MANUEL USE :
To use C1 relay, display must be in start menu. Whether LOCK mod (Ref.
LOCK menu) is selected or not, if pressed Down ( ) button for 3 sec.; at
the end of 3 sec.; if relay is on, it will be off and if relay is off, it will be on.
SET
SET
SET
SET
SET
ESC
SET
SET
SET
ESC
SET
SET
SET
SET
Main Display
SU
C2:
C1:
00
02
04
06
08
10
12
14
16
22
20
18
24
SET
SET
SET
ESC
SET
SET
SET
ESC
SET
SET
SET
SET
SET
Main Display
SU
C2:
C1:
00
02
04
06
08
10
12
14
16
22
20
18
24
SET
SET
SET
ESC
SET
SET
SET
ESC
SET
SET
SET
SET
SET
Main Display
SU
C2:
C1:
00
02
04
06
08
10
12
14
16
22
20
18
24
Date
Time
Relay on/off situation
Lock Mode
ESC button
SET button
UP button
DOWN button
It represents the time
interval which relay will
switch ON.