MULTIMETER

EPM-04 / 04C / 04CS

Press SET button for 3 sec.
(trA Fo menu is displayed.)

Find “SP CUr rnt / SP UoL t”
menu by scrolling
UP-DOWN buttons. 

SET

SET

Press SET button, “SP CUr Hý / SP UoL Hý”
menu is displayed.

Press SET button [(I-H L-1/I-L L-1) /
(U-H L-1/U-L L-1) menu is displayed.]

Press SET button. Blinking the first digit of
displayed value appears.

Press ESC button one by one until “SAU E  SEt  yES” is displayed.

Press SET button. When “SAU E  SEt  yES” is displayed (If you press
ESC button or choose “no” option instead of “yES” then new data will
be cancelled and previous value will be activated).

SET

SET

ESC

SET

Find [(SP CUr Hý/SP CUr Lo) / (SP UoL
Hý/SP UoL Lo)]

 menu by scrolling UP-

DOWN buttons.

Auto Reset Function :

If 

Auto Reset

 function is selected as ON;

Each time that the current decreases “50mAxCtr” value,
start-up delay time is reset and when the current value
increases “50mAxCtr”, start-up delay function is
activated.
If 

Auto Reset

 function is selected as OFF;

If the power supply is switched 

off

 and then switched

on

, start-up delay function is activated.

Start-up delay:

Start Delay Time is used to prevent from faulty
switchings  caused by motor start-up current
(demurrage current).
Out1 remain switched ON in this time period (When
U-I is selected); In this time period, even if the current
value exceeds the limits device doesn’t sense it as a
warning. The device doesn’t give a warning even if the
current value isn’t in the setting interval.
This function is used with “Auto Reset” function.

Press SET button. When “SAU E  SEt  yES” is displayed (If you press
ESC button or choose “no” option instead of “yES” then new data will
be cancelled and previous value will be activated).

Find “SP CUr rnt / SP UoL t”
menu by scrolling UP-DOWN buttons.

Press SET button (SP CUr Hý / SP Uol Hý
menu is displayed.)

Press SET button [(CUr ýnS trP on /
AUt o rSt on) / UoL ýnS trP off] is displayed.

Select “on” in order to activating the “instant trip function” (AUt o rSt),
select “off” in order to disactivating the “instant trip function”, by scrolling
UP/DOWN buttons.

Press SET button, [(CUr ýnS trP / AUt o rSt) / UoL ýnS trP] is displayed.
(Selection is entered but is not activated yet. For activating the new
selection, please follow the below steps).

Press ESC button one by one until “SAU E  SEt  yES” is displayed.

SET

SET

SET

SET

ESC

SET

Find [(CUr ýnS trP / AUt o rSt) / UoL ýnS trP]
menu by scrolling UP-DOWN buttons.

Press SET button for  3 sec.
(trA Fo menu is displayed)

In this menu, high set points for voltage values are
programmed. Hý values for Phase-Neutral / Phase-
Phase (according to Star / Delta selection) can be
entered one by one.

Note:

 High Voltage  values are programmed for

(Phase-Neutral / Phase-Phase) separately but “Hý
HyS” (hysteresis) and “Hý ond” (delay on time) and
“Hý oFd” (delay off time) values are common; these
parameters have same values for Phase-Neutral /
Phase-Phase.
When Connection type (Star/Delta) is selected (refer
to Connection menu), device will change the
U-H L-1, U-H L-2 and U-H L-3 values automatically
according to connection.

If all the voltage values (Phase-Neutral / Phase-Phase)
are under the Hý value; releated relay is switched on,
its LED turned 

on

 (please refer “Output”) and releated

H LEDs are turned 

off

.

If all the voltage values (Phase-Neutral / Phase-Phase)
are over the Hý value, H LED blinks and releated output
is switched off at the end of “delay on time” (U-H ond),
its LED turned 

off

 (please refer “Output”) and releated

H LEDs are turned 

on

.

If all voltage (Phase-Neutral / Phase-Phase) are below
the high set value (Hi) as a hysteresis voltage (U-H HyS),
releated output is switched on at the end of the “delay
off time” (U-H oFd), its LED turned 

on

 (please refer

“Output”) and H LED is turned 

off

.

Programming “SP UoL t” :

Using purposes of submenus of “SP UoL t” explained below with
details.

Example :

 If the connection type is selected as Star

(with neutral); U-H HyS=10V U-H L-1=250V,
U-H L-2=255V, U-H L-3=260V
and then this connection type is selected as Delta
(without neutral), device will change the values after
calculated them according to Phase-Phase values.

New values;

U-H L-1 (L1-L2 Phase to phase voltage) = 433 V
U-H L-2 (L2-L3 Phase to phase voltage) = 441 V
U-H L-3 (L3-L1 Phase to phase voltage) = 450 V
U-H-HyS = 10 V.

T h e r e   a r e   6   s u b m e n u s .
U - H   L - 1 ,   U - H   L - 2 ,   U - H   L - 3 ,   U - H   H y S ,
U - H   o n d ,   U - H   o F d .

4

Programming “CUr ýnS trP”, “AUt o rSt” and “UoL ýnS trP”

Programming the “SP CUr Hý”, “SP CUr Lo”, “SP UoL Hý” and “SP UoL Lo”.

Enter the blinking digit
value by scrolling
UP/DOWN buttons.
Switch to the other digits
by using SET button, use
ESC button to go to previous digit. After you entered the last digit
press SET button, “I-H L-1/I-L L-1) / (U-H L-1/U-L L-1” is displayed.
(Data is entered but is not activated yet. For activating the new data
please follow the below steps).

SET

Instant Tripping Function.

At position 

ON

, if any phase current (

I

L1, 

I

L2, 

I

L3 and

I

N) exceeds 1.5 times of high (I-H L-1, I-H L-2, I-H L-

3, I-H L-n) values, the “current output” switches 

off

instantly, output LED turned 

off

 and H LEDs for related

currents turned 

on

. (Please refer to 

“Output”

.)

At position 

OFF

, if any phase current (

I

L1, 

I

L2, 

I

L3 and

I

N) decrease 0.5 times of low (I-L L-1, I-L L-2, I-L L-3,

I-L L-n) values, the “current output” switches 

off

instantly, output LED turned 

off

 and L LEDs for related

currents turned 

on

. (Please refer to 

“Output”

.)

At position 

OFF

, instant tripping function is cancelled.

MULTIMETER

EPM-04 / 04C / 04CS

Low value for L1, when the Star is
selected; low value for L1-L2, when the
Delta selected can be defined in this
menu.
0....300 for Star connection and
0....500 for Delta connection can be
defined.
If the value is set to zero (0), the high
voltage warning is disabled. Refer 

“SP

Uol Lo” for details.

Note:

 L2 and L3 phases can be

programmed similarly.

(Refer to Page-4 for 

SP CUr Hý, SP CUr Lo,

SP UoL Hý ve SP UoL Lo

)

When Connection type (Star/Delta) is selected (refer
to Connection menu), device will change the
U-L L-1, U-L L-2 and U-L L-3 values automatically
according to connection.

In this menu, low set points for voltage values are
programmed. Lo values for Phase-Neutral / Phase-
Phase (according to Star / Delta selection) can be
entered one by one.

Example :

 If the connetion type is selected as Star

(with neutral); U-L-Hys=10V
U-L L-1=180V, U-L L-2=175V, U-L L-3=170V
and then this connection type is selected as Delta
(without neutral), device will change the values after
calculated them according to Phase-Phase values.

New values;

U-L L-1 (L1-L2 Phase to phase voltage) = 311 V
U-L L-2 (L2-L3 Phase to phase voltage) = 303 V
U-L L-3 (L3-L1 Phase to phase voltage) = 294 V
U-L-HyS = 10 V.

If all the voltage values (Phase-Neutral / Phase-Phase)
are over the Lo value; releated output is switched 

on

,

its LED turned 

on

 (please refer “Output”) and releated

L LEDs are turned 

off

.

If any of the voltage valueses (Phase-Neutral / Phase-
Phase) decrease the Lo value, L LED blinks and
releated output is switched 

off

 at the end of “delay

on time” (U-L ond), its LED turned 

off

 (please refer

“Output”) and releated L LED is turned 

on 

continuously.

If all voltage (Phase-Neutral / Phase-Phase) values
increase the low set value (Lo) as a hysteresis voltage
(U-L HyS), releated relay is switched 

on

 at the end of

the “delay off time” (U-L oFd), its LED turned 

on

 (please

refer “Output”) and L LED is turned 

off

.

Note:

 Low Voltage  values are programmed for (Phase-

Neutral / Phase-Phase) separately but “U-L HyS”
(hysteresis), “U-L ond” (delay on time) and “U-L oFd”
(delay off time) values are common; these parameters
have same values for Phase-Neutral / Phase-Phase.

High value for L1, when the Star is
selected; high value for L1-L2, when the
Delta selected can be defined in this
menu.
0....300 for Star connection and
0....500 for Delta connection can be
defined.
If the value is set to zero (0), the high
voltage warning is disabled. Refer 

“SP

Uol Hý” for details.

Note:

 L2 and L3 phases can be

programmed similarly.

In this menu, required hysteresis voltage
for high voltage warning is programmed.
(same for Phase-Neutral/Phase-Phase.)
0....200V for Star connection and
0....200V for Delta connection can
be defined.
Refer 

“SP UoL Hý” for details.

In this menu, required hysteresis voltage
for low voltage warning is programmed.
(same for Phase-Neutral/Phase-Phase.)
0....200V for Star connection and
0....200V for Delta connection can
be defined.
Refer 

“SP UoL Lo” for details.

Press SET button for 3 sec.
(trA Fo menu is displayed.)

SET

SET

Press SET button (SP UoL Hý / SP CUr Hý
menu is displayed.)

Press SET button [(U-H L-1/U-L L-1) / (I-H
L-1/I-L L-1) menu is displayed.]

Press SET button. Blinking the first digit of
displayed value appears.

Press ESC button one by
one until “SAU E  SEt  yES”
is displayed.

SET

SET

ESC

SET

Find [(SP UoL Hý / SP UoL Lo) / (SP CUr Hý
/ SP CUr Lo)] 

menu by scrolling

UP-DOWN buttons

Find [(U-H HyS / U-L HyS) / (I-H HyS / I-L HyS)] menu by scrolling
UP-DOWN buttons.

“Delay on” time for activating the output for
high voltage warning. It is common for all
voltages (same for Phase-Neutral/Phase-
Phase.)
The  value can be programmed between
000,0 and 999,9 in terms of seconds.

(

Refer 

“SP UoL Hý” for details.)

“Delay on” time for activating the output for
low voltage warning. It is common for all
voltages (same for Phase-Neutral/Phase-
Phase.)
The  value can be programmed between
000,0 and 999,9 in terms of seconds.

(

Refer 

“SP UoL Lo” for details.)

“Delay off” time for activating the output for
high voltage warning. It is common for all
voltages (same for Phase-Neutral/Phase-
Phase.)
The  value can be programmed between
000,0 and 999,9 in terms of seconds.

(

Refer 

“SP UoL Hý” for details.)

“Delay off” time for activating the output for
low voltage warning. It is common for all
voltages (same for Phase-Neutral/Phase-
Phase.)
The  value can be programmed between
000,0 and 999,9 in terms of seconds.

(

Refer 

“SP UoL Lo” for details.)

5

Programming the “U-H HyS”, “U-L HyS”, “I-H HyS”, “I-L HyS”

Press SET button for 3 sec.
(trA Fo menu is displayed.)

SET

SET

Press SET button (SP UoL Hý / SP CUr Hý
menu is displayed.)

Press SET button [(U-H L-1 / U-L L-1) /
(I-H L-1 / I-L L-1) menu is displayed.]

SET

Find [(SP UoL Hý / SP UoL Lo) / (SP CUr Hý
/ SP CUr Lo)] 

menu by scrolling

UP-DOWN buttons.

L1

L2

L3

Find [(U-H ond / U-H oFd / U-L ond / U-L oFd) / (I-H ond / I-H oFd / I-L
ond / I-L oFd)] 

menu by scrolling UP-DOWN buttons.

Programming the “U-H ond”, “U-H oFd”, “U-L ond”, “U-L oFd”,
“I-H ond”, “I-H oFd”, “I-L ond”, “I-L oFd”.

Enter the blinking digit value by
scrolling UP/DOWN buttons.
Switch to the other digits by using
SET button, use ESC button to go to
previous digit. After you entered the last
digit press SET button,
[(U-H HyS / U-L HyS) / (I-H HyS / I-L HyS)]

 is displayed. (Data is

entered but is not activated yet. For activating the new data please
follow the below steps).

SET

Please refer to below graphics for the operating
principle of StA rt dEL and Aut o rSt  functions

T h e r e   a r e   6   s u b m e n u s .
U - L  L - 1 ,   U - L   L - 2 ,   U - L   L - 3 ,   U - L   H y S ,
U - L   o n d ,   U - L   o F d .

Find “SP UoL t / SP CUr”
menu by scrolling
UP-DOWN buttons.

Press SET button. When
“SAU E  SEt  yES” is
displayed (If you press ESC button or choose “no” option instead of “yES”
then new data will be cancelled and previous value will be activated).

Find “SP UoL t / SP CUr”
menu by scrolling
UP-DOWN buttons.

Hi ond  = 10 sn.

Lo ond = 10 sn.

Hi ofd =   5 sn.

Lo ofd  =   5 sn.

Start

= 15 sn.

L1 Hi

= 3A

L1 Lo  = 1A

Ins. trp  = on

Start

Start

Start

t(s)

Start

Start

Start

5 A

4 A

3 A

2 A

1 A

Un (on)

Un (off)

I L1

Hi
ond

Hi
ond

Hi
ofd

Hi
ond

t(s)

t(s)

t(s)

t(s)

t(s)

Hi
ond

Hi
ond

Hi
ofd

Hi
ofd

Lo
ofd

Ins.
t r p .

Lo
ond

Lo
ofd

Lo ond

10

20 30

40

50

60

70 80

90 100 110 120 130 140 150 160 170 180 190 200

Lo
ofd

Lo
ofd

Ins.
t r p .

Switch-on

Switch-off

Switch-on

Switch-off

Out1

Out2

Auto

on

Auto

of

Out1

Out2

Switch-on

Switch-off

Switch-on

Switch-off