background image

27

28

Flasher :

Single Shot

Summary of Contents for MCB-200

Page 1: ...6698 Rev 2 www entes com tr MCB 200 MULTIFUNCTION DIGITAL TIME RELAY With 1 CO contact Operating Manual Dudullu OSB 1 Cadde No 23 34776 Umraniye ISTANBUL TURKEY Tel 90 216 313 01 10 Fax 90 216 314 16 15 ...

Page 2: ...e time adjustment range between 0 2 9999 seconds and 0 1 9999 minutes MCB 200 has 15 different functions with wide adjustable time ranges The main application area is the industrial and automation control systems Wide supply voltage range and one output relay with C O contacts offer the highest flexibility for many applications MCB 200 has two dry contacts for START and STOP inputs 1 1 Product Fea...

Page 3: ...Start Indicates that stop input is active 11 When R1 or R2 relays are activated the center of the circles are turned on R and L letters are used to indicate left or right direction when inverser relay function is selected Star Delta Indicate the output relay state in Star Delta function 12 Indicates the time type of functions 13 In the main menu it shows the elapsed time 14 In the main menu it sho...

Page 4: ... When user shorts two terminals An Example This function needs td delay time to release relay When stop input is applied it stops counting and saves the time t1 With stop input s trailing edge counting continues from the saved time t1 until delay time td Here td t1 t2 While stop input is active the relay doesn t change its position 5 2 OPERATING INSTRUCTIONS When the device is taken out of the box...

Page 5: ...ap is shown below There are two main submenus as function selection and display settings Function Selection Submenu A new function is set from function selection menu In this submenu user chooses a function sets t parameter parameters for selected function assigns relay output Display Configurations Submenu Changing password adjusting contrast activating backlight or changing language is done from...

Page 6: ...tivated until next start pulse is applied 3 Off Delay Start by external trigger trailing edge This function is controlled by start input Output Relay is activated when start pulse is applied and remain on time counting starts with the trailing edge and output relay is deactivated at the end of delay time td lf trigger pulse occur during time counting period elapsed time is reset R S OFF ON NO C td...

Page 7: ...s activated and remain on during ton After that it is deactivated and toff starts This cycle is repeated while start pulse is on high 5 Symmetric Flasher Start by external trigger leading edge Relay OFF start Function is similar to the ON Start version function 4 with the exception that the output relay start as passive ON KAPALI S R NO C OFF OFF S R NO C ON ...

Page 8: ... edge output relay is activated and remain on during ton After that it is deactivated and toff starts This cycle is repeated while start pulse is on high 7 Asymmetric Flasher Start by external trigger leading edge Relay ON start Function is similar to the ON Start version function 6 with the exception that the output relay start as passive S R NO C OFF ON toff toff toff toff toff ton ton ton ton t...

Page 9: ...deactivated and toff starts This cycle is repeated until the next edge retrigger pulse If a trigger pulse occur during ton time counting is reset and ton time counting is restarted 9 Symmetric Flasher Start by external edge retrigger Relay OFF start Function is similar to the ON Start version function 8 with the exception that the output relay start as passive ON KAPALI S R NO C OFF ON KAPALI S R ...

Page 10: ...t ton and toff times can be set differently 11 Asymmetric Flasher Start by external edge retrigger Relay OFF start Function is similar to the Symmetric version function 9 with the exception that ton and toff times can be set differently R S OFF ON NO C ton ton ton ton ton toff toff toff toff R S OFF ON NO C toff toff toff toff toff ton ton ton ton ton t ...

Page 11: ...ed function will be reset 13 Adjustable and Resettable ON Delay Pulse by external trigger leading edge This function is controlled by start input The cycle starts with adjustable toff delay time after a pulse is created at the Start input At the end of delay time output relay is activated and remain activated during ton If a re trigger pulse occurs during toff elapsed time is reset and toff counti...

Page 12: ...emain on during td 15 Adjustable OFF Delay Pulse by External Trigger Leading Edge Re trigger This funcition is controlled by start input The cycle starts with adjustable td delay time and output relay is activated It remains activated during this period If a re trigger pulse occurs during td period elapsed time is resett and td counting is restarted S ON OFF R NO C t t S ON OFF R NO C t t ...

Page 13: ...ection Function sub menu is reached by pressing SET button in Settings menu The functions that the device offers can be browsed with UP or DOWN buttons The user selects the desired function enters its adjustment menu by pressing SET button ...

Page 14: ...nd DOWN button to decrease The user presses SET button to move to the next digit on the right and the ESC button to move back to a previous digit After entering a number user selects unit minutes or seconds by pressing UP or DOWN Finally the selected values are stored by pressing SET button FUNCTION SETTINGS ON Delay Example Interval 0 1 9 9 Example Interval 10 9999 0000 SET ESC 0000 SET ESC 0030 ...

Page 15: ...27 28 Flasher Single Shot ...

Page 16: ...ngs In password submenu user can activate or deactivate the password To change password user enters current password first then new password twice User can change contrast level from 1 to 5 Also user can choose the backlight operation as on off on for 5 seconds Five languages as Turkish English German French Spanish can be selected ...

Page 17: ...e scale Second line displays the elapsed time value min icon indicates the time scale start icon indicates that Strt Input is active The number 01 indicate that 1st function is selected icon is turned on and indicate that R1 relay is activated When UP or DOWN button is pressed while on the main menu the name of the selected function is displayed By pressing the ESC button main display is accessed ...

Page 18: ...e between all isolated circuits Pollution Category Overvoltage Category 2 dry contacts Start Stop Selectabale 0 2 9999 seconds 0 1 9999 minutes 100 ms 0 2 of the set time 0 5 1 C O Contact 8 A 2000VA 250 V 1x 10 6 Width 36 0 mm Length 90 0 mm Depth 59 7 mm 2 5mm 2 stranded 4 0mm2 solid 0 25 kg Ray Montaj IP40 IP20 5 50 C IEC 61812 1 10 1996 EN 61812 1 A11 8 1999 DIN VDE 0435 part 2021 2004 108 EC ...

Page 19: ...35 36 ...