38
IP2159EN - 2017-06-12
Output
Description
+24V DC
GND
3 ...
13
Output for the power supply to the accessories 24V 400 mA max.
NB: the maximum absorption of 400 mA corresponds to the sum of all the accessories installed.
1 2
Output for connecting an electric lock / electric strike.
Select the type of electric lock / electric strike using DIP1.
NOTE1: do not use electric locks / electric strikes with a reset feature.
NOTE2: with DIP2 in OFF and no COM400 function selector switch (or the latter in two-way mode), output 1-2 is perma-
nently powered so that the electric lock / electric strike can always open the door. If, on the other hand, you want to lock
the door wing with the door closed, set the selector to one-way mode or make a jumper GND-EXIT (3-11). In this condi-
tion, output 1-2 is powered throughout the operation (from opening until complete closure); for this reason, locks with
mechanical reset cannot be used. With DIP2 in ON, the behaviour will be the same except for the fact that output 1-2 will
always be unpowered in two-way mode and throughout the open/close operation in one-way mode”.
OPEN
EXIT
OFF
GND
3 ... 10 11 12
Output for connecting the function selector switch.
If the function selector switch is on OFF, the Push and Go function is disabled.
If a function selector switch is installed, disconnect the ON/OFF/HOLD switch (if present).
BATTERY
BATTERY KIT
If no mains power supply is available, the battery kit will guarantee operation in "energy-saving" mode.
If no mains power supply is available, the door only operates with the key switch connected to 3 GND -6 KEY.
In “energy-saving” mode, the door can remain stationary for up to a week while waiting for the KEY command.
The following sensors are not active during “energy saving” operation:
-OPD motion sensor
-PIMP reversal safety contact
-PDET opening safety device
In this mode (on automations connected in parallel), connect the batteries only to the MASTER automation fitted with
DAB905ESE.
By changing the pre-configured parameter group, you can set the battery kit to CONTINUITY mode. If no mains power
supply is available, the door operates normally until the batteries are fully discharged.
In this mode, on automations connected in parallel, connect the batteries on both automations equipped with DAB905ESE.
NB: for charging purposes, the battery kit must be connected to the control panel at all times.
A new kit with fully-charged batteries can usually open and close a door consecutively in CONTINUITY mode.
If you want to check the battery kit is working correctly, set DIP5=ON.
In the event of a battery alarm, the DAB105CU control panel LED will flash twice.
An acoustic/light alarm signal can be connected to terminals 6-7-8 on the DAB905ESA card.
17.3. Adjustments
17.2 Outputs and accessories
Trimmer
Trimmer
Description
Adjustment of the opening delay time, from 0 s to 3 s.
With DIP3=ON, the door release is active throughout the opening delay.
Dip-switches
DIP
Description
OFF
ON
DIP1
Power supply to the electric lock / electric
strike.
12 V max 500 mA
24 V max 250 mA
DIP2
Type of electric lock / electric strike.
DO NOT USE ELECTRIC LOCKS / ELEC-
TRIC STRIKES WITH A RESET FEATURE.
Normal
When it is powered, the door can be
opened.
Anti-panic
When it is unpowered, the door can be opened.
DIP3
Release
Disabled
Enabled during the time set by the delay time
adjustment trimmer.
DIP4
Electric lock / electric strike coupling
Disabled
Enabled
When it approaches the closing stop, the door
increases its force/speed to ensure correct
closure on the electric lock / electric strike.
DIP5
Battery test
Disabled
Enabled
Jumper
Description
OFF
ON
J
Emergency closure reset
Manual
Automatic
For more information, refer to the COM400MKB-MHB selector manual.
i