background image

Model: EP.MINI

MiNi Description 

MiNi Reader 

Keypad Display Unit

Encrypted Lock Control

(ELC) 

ENTRY

PASS

5

Summary of Contents for EP.MINI

Page 1: ...ENTRYPASS EP MINI Wiring Guide Version 1 00 Last Updated 09 01 2010 1...

Page 2: ...tryPass Platform1 Access Control System 10 Digit Card Number System cater for 10 digit card number installation For EntryPass Platform1 Access Control System to work correctly both control panel and s...

Page 3: ...iliar with your system configuration and should be able to answer any of your questions Should you need additional information please call our Technical Support Help desk Monday to Friday 9 00 AM to 6...

Page 4: ...w the instruction below Observe precautions while handling the circuit board assembly by using proper grounding straps and handling precautions at all Visually ensure no onboard parts is broken damage...

Page 5: ...Model EP MINI MiNi Description MiNi Reader Keypad Display Unit Encrypted Lock Control ELC ENTRYPASS 5...

Page 6: ...lack GND 0VDC Grey Yellow NO1 White Blue CM1 White NC1 Brown NO2 Grey CM2 Green NC2 Purple 12Vdc Lock Purple 12Vdc Lock MiNi Reader Color Description Red 12VDC Black GND 0VDC Pink Door Sensor Black GN...

Page 7: ...Model EP MINI MiNi reader keypad display unit ENTRYPASS White LCD Display Enter Key Numbered Keypad Navigation Pad LED Indicator 7...

Page 8: ...Power Supply Unit Specification ENTRYPASS 8 Model EP MINI Power Supply Unit Specification Switching Power Supply 12V DC 3 Amp Minimum ENTRYPASS...

Page 9: ...S 0 V 12 VDC Switching Mode Power Supply Unit 12V DC 3A Minimum Red 12VDC Black Gnd Red 12VDC Black Gnd Blue RTX Blue RTX Orange RCLK Orange RCLK Yellow RDAT Yellow RDAT The distance from MINI keypad...

Page 10: ...NTRYPASS White Blue CM1 White NC1 0V Emergency Breakglass Emergency Keyswitch Electro Magnetic Lock Purple 12VDC Purple 12VDC Switching Mode Power Supply Unit 12V DC 3A Minimum Diode 1N4002 must be in...

Page 11: ...PASS 11 Diode 1N4002 must be installed at the locking devices in order to protect against back EMF White Blue CM1 Grey Yellow NO1 0V Electro Magnetic Lock Drop Bolt Purple 12VDC Purple 12VDC Switching...

Page 12: ...r Sensor and Door Release Button Push Button ENTRYPASS The distance from door sensor to MINI and from push button to ELC should not more than 30 meter 12 Door Sensor Push Button Pink Door Sensor Black...

Page 13: ...e programming mode To configure MINI as a READER Mode press F1 123456 01 Enter 01 Enter 05 Enter 1 Enter ESC x3 To configure NMINI as a READER Mode press F1 123456 01 Enter 01 Enter 04 Enter 1 Enter E...

Page 14: ...Party Reader ENTRYPASS 0 V 12 VDC Green D0 White D1 Black Gnd Red 12VDC Green D0 White D1 Exit Reader Black Gnd Red 12VDC Switching Mode Power Supply Unit 12V DC 3A Minimum The distance from MINI to...

Page 15: ...255 7 08 255 255 255 8 09 255 255 255 9 10 255 255 255 10 11 255 255 255 11 12 255 255 255 12 13 255 255 255 13 14 255 255 255 14 15 255 255 255 15 To configure MINI unit address default 00 press F1...

Page 16: ...232 mode ENTRYPASS The distance from computer to MINI should not more than 10 meter DB 9 Female Connecter White to Pin 2 Green to Pin 3 Black to Pin 5 Green RS 232 RX White RS 232 TX Black Gnd EntryPa...

Page 17: ...than 1 MINI to be connected to the PC using the same bus comport the unit address for each MINI must be unique Only a total of 16 controllers can be connected to each bus comport Purple C Purple C Gre...

Page 18: ...Model EP MINI Connecting to the power supply unit ENTRYPASS 0 V 12 VDC Red Yellow 12VDC Black Gnd Switching Mode Power Supply Unit 12V DC 3A Minimum 18...

Page 19: ...Exit Reader Black Gnd Red Yellow 12VDC 12 VDC Switching Mode Power Supply Unit 12V DC 3A Minimum EntryPass Platform1 Server Access Control System White NC1 Orange RCLK Yellow RDAT Blue RTX Pink Push...

Page 20: ...rol System please make sure all the wiring connection is correct On the MINI keypad please make sure the following setting has been done Format Memory Unit Address Advisable to perform format memory f...

Page 21: ...mode 01 Enter 02 Enter 01 Enter 1 Enter Press 1 to set it ON or press 0 to set it OFF ESC X3 Security Mode Enter programming mode 01 Enter 02 Enter 02 Enter 0 Enter Press 1 to set it ON or press 0 to...

Page 22: ...ming mode 01 Enter 02 Enter 15 Enter Key in the new open time 00 99 ESC X3 Pin Trials Enter programming mode 01 Enter 02 Enter 16 Enter Key in the new pin trials 00 09 ESC X3 Card Pin Tz Enter program...

Page 23: ...all the cards to be deleted card by card ESC X4 Reset Card Pin Enter programming mode 02 Enter 01 Enter 06 Enter Key in the card number that need to perform pin reset 6 digits ESC X3 Reset Lockout En...

Page 24: ...et it OFF ESC X3 Inhibit Mode Enter programming mode 01 Enter 02 Enter 01 Enter 1 Enter Press 1 to set it ON or press 0 to set it OFF ESC X3 Security Mode Enter programming mode 01 Enter 02 Enter 02 E...

Page 25: ...01 Enter 02 Enter 14 Enter Key in the new card pin timezone ESC X3 Date Setting Enter programming mode 01 Enter 03 Enter Key in the new date DDMMYY ESC X2 Time Setting Enter programming mode 01 Enter...

Page 26: ...06 Enter Key in the card number that need to perform pin reset 10 digits ESC X3 Reset Lockout Enter programming mode 02 Enter 01 Enter 07 Enter 1 Enter ESC X3 Reset Lockout Time Enter programming mod...

Page 27: ...ta Signal Max Distance Description MINI to ELC 10m 30 ft 22 AWG 3 Pairs Shielded Computer to PC Communicator RS 232 10m 30 ft 22 AWG 2 Pairs Shielded PC Communicator to MINI RS 485 1000m 3000 ft 22 AW...

Reviews: