ENTRYPASS TECHNICAL – WIRING GUIDE

Diode(1N4002) must be installed at the locking devices in order to protect against back EMF

-

+

NO1

COM1

Striker Lock or Drop Bolt

+

Lower Connector

I1D0

I1D1

LED1 BUZ1

IN1

IN2

GND NC1 COM1 NO1

NC2

NO2

COM2

VR1+ GND O1D0 O1D1 LED2 BUZ2

IN3

IN4

GND

C3-

C3+

C2-

C2+

C1-

C1+

+12V

GND

PSU

Connecting the Striker Lock or Drop Bolt (NO)

Summary of Contents for EP.N5150

Page 1: ...Copyright Entrypass Corporation ENTRYPASS TECHNICAL WIRING GUIDE Version 1 18 Last Updated 18 07 2018 HCB WIRING GUIDE EP S3150 EP N5150 EP S3200 EP N5200 EP S3400 EP N5400 ...

Page 2: ...S3150 S3200 S3400 N5150 N5200 and N5400 support HID AGK00 09 10 11 14 19 20 Wiegand Multi Bit Keyed Card Pin N5150 N5200 and N5400 support AES Encryption S3200 S3400 N5200 N5400 support event trigger See http www entrypass net for updates revisions and download the latest installation manual Platform1 version 3 support 6 and 10 digits format For existing site P1 will detect its card database to de...

Page 3: ...act your system installer Your installer is familiar with your system configuration and should be able to answer any of your questions Should you need additional information please call our Technical Support Help desk Monday to Friday 9 00 AM to 6 00 PM GMT 8 00 Method Details Phone 60 3 8068 1929 Fax 60 3 8068 1922 Internet www entrypass net Email support entrypass net BEFORE YOU BEGIN ...

Page 4: ...ease follow the instruction below Observe precautions while handling the circuit board assembly by using proper grounding straps and handling precautions at all Visually ensure no onboard parts is broken damage or contains burn mark Do not turn on the power supply until you completed all wiring and external add on devices installations Instances of Non Warranty Damage due to natural disaster accid...

Page 5: ...ector Relay LEDs Supply Voltage Selector Relay LEDs Buzzer Relay 1 Relay 2 Buzzer ON OFF MCU Battery Address Dip Switch Cold Start Switch Reset Switch COM Rx Tx LEDs RS232 COMs Heartbeat LED RS485 COMs Network Port Cold Start Factory Default and AES Hard reset Selection Jumper Components Description ...

Page 6: ...RS485 COM2 Connection C2 RS485 COM2 Connection C1 RS485 COM1 Connection C1 RS485 COM1 Connection I1D0 Reader 1 Data 0 Input I1D1 Reader 1 Data 1 Input LED1 Reader 1 LED BUZ1 Reader 1 Buzzer IN1 Input 1 Default Door Sensor IN2 Input 2 Default Exit Push Button GND Inputs Ground NC1 Relay 1 Normally Close Connection COM1 Relay 1 Common Input NO1 Relay 1 Normally Open Connection NC2 Relay 2 Normally C...

Page 7: ...zer IN5 Input 5 IN6 Input 6 NC3 Relay 3 Normally Close Connection COM3 Relay 3 Common Input NO3 Relay 3 Normally Open Connection NC4 Relay 4 Normally Close Connection COM4 Relay 4 Common Input NO4 Relay 4 Normally Open Connection VR2 Supply Voltage Positive Connection 12V 5V GND Supply Voltage Ground Connection O2D0 Reader 4 Data 0 Input O2D1 Reader 4 Data 1 Input LED4 Reader 4 LED BUZ4 Reader 4 B...

Page 8: ...y Earthing ACC AC Fail Monitoring BAT BS Backup Battery Monitoring 12V 12V GND ETH ACC BAT BS Power Supply Connector BAT BS Backup Battery Monitoring point will monitor the backup battery voltage which will supply power to the board when AC power is cut off The minimum voltage for cutoff while using backup battery is 10 8V Legend Description ...

Page 9: ...Copyright Entrypass Corporation ENTRYPASS TECHNICAL WIRING GUIDE ENTRYPASS Power Supply Unit Specification Switching Power Supply 12V DC 3 Amp Minimum Power Supply Unit Specification ...

Page 10: ...Lower Connector I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2 COM2 VR1 GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3 C3 C2 C2 C1 C1 12V GND PSU Diode 1N4002 must be installed at the locking devices in order to protect against back EMF It is advisable to connect EM lock COM to 12Vof PSU Power Supply Unit Connecting the Lock NC Breakglass and Keyswitch ...

Page 11: ...stalled at the locking devices in order to protect against back EMF NO1 COM1 Striker Lock or Drop Bolt Lower Connector I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2 COM2 VR1 GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3 C3 C2 C2 C1 C1 12V GND PSU Connecting the Striker Lock or Drop Bolt NO ...

Page 12: ...etic Lock 2 Lower Connector I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2 COM2 VR1 GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3 C3 C2 C2 C1 C1 NC1 12V GND PSU Emergency Breakglass 2 Emergency Keyswitch 2 Diode 1N4002 must be installed at the locking devices in order to protect against back EMF Connecting the Lock NC Breakglass and Keyswitch 2 Doors Mode Only ...

Page 13: ... or Drop Bolt 2 Lower Connector I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2 COM2 VR1 GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3 C3 C2 C2 C1 C1 NO1 12V GND PSU Connecting the Lock NO Breakglass and Keyswitch 2 Doors Mode Only Diode 1N4002 must be installed at the locking devices in order to protect against back EMF ...

Page 14: ...3 Upper Connection I2D0 I2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4 COM4 VR2 GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND 12V GND PSU Diode 1N4002 must be installed at the locking devices in order to protect against back EMF NC1 and NC2 connection for 4 Doors Mode please refer to 2 Doors Mode NC connection 4 Doors Mode only applicable for N5400 and S3400 Connecting the Lock NC Breakglass and Keyswi...

Page 15: ...5 IN6 GND NC3 COM3 NO3 NC4 NO4 COM4 VR2 GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND 12V GND PSU Connecting the Lock NO Breakglass and Keyswitch 4 Doors Mode Only Diode 1N4002 must be installed at the locking devices in order to protect against back EMF NO1 and NO2 connection for 4 Doors Mode please refer to 2 Doors Mode NO connection 4 Doors Mode only applicable for N5400 and S3400 ...

Page 16: ...PASS TECHNICAL WIRING GUIDE Push Button IN1 IN2 GND Door Sensor Lower Connector I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2 COM2 VR1 GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3 C3 C2 C2 C1 C1 Connecting the Door Sensor and Push Button ...

Page 17: ...Push Button 1 IN1 IN2 GND Door Sensor 1 Lower Connector I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2 COM2 VR1 GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3 C3 C2 C2 C1 C1 IN3 IN4 GND Push Button 2 Door Sensor 2 Connecting the Door Sensor and Push Button 2 Doors Mode ...

Page 18: ...2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4 COM4 VR2 GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND IN7 IN8 GND Push Button 4 Door Sensor 4 IN1 2 3 4 Connections for 4 Doors Mode please refer to 2 Doors Mode IN1 2 3 4 connections 4 Doors Mode only applicable for N5400 and S3400 Connecting the Door Sensor and Push Button 4 Doors Mode ...

Page 19: ...ctor I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2 COM2 VR1 GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3 C3 C2 C2 C1 C1 Upper Connection I2D0 I2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4 COM4 VR2 GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND Reader 3 Reader 4 Reader 3 and Reader 4 only applicable for N5400 and S3400 Connecting the Reader 3rd Party Reader ...

Page 20: ...ND Black D1 White D0 Green GND C3 C3 C2 C2 C1 C1 Power Supply Unit 12VDC 1A Power Supply Unit 12VDC 1A Network Switch BioEntry P2 R2 BioEntry P2 R1 Cat 5e Connecting the Reader Suprema V2 Devices Support the following Suprema V2 devices 1 BioStation A2 2 BioStation 2 3 BioStation L2 4 BioEntry W2 5 BioEntry P2 6 BioLite N2 Each of the Suprema device require power of 12VDC 500mA 1A depend on the mo...

Page 21: ...NO1 NC2 NO2 COM2 VR1 GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 12V Red GND Black Wiegand GND Black D1 White D0 Green GND C3 C3 C2 C2 C1 C1 Power Supply Unit 12VDC 1A Power Supply Unit 12VDC 1A Network Switch BR100 R2 BR100 R1 Cat 5e Connecting the Reader Entrypass BR100 Devices Each of the BR100 device require 12VDC 1A power supply ...

Page 22: ...rlock purpose An interlock input and interlock relay need to be assigned using Platform1 Server for cross board interlock on each controller Please configure the interlock input as Open Trigger in Platform1 Server if interlock input is connected with NC relay output Advisable to use analog input for detecting line open condition The cabling distance for cross board interlock connection can up to 1...

Page 23: ...ss 1 S3150 S3200 S3400 2 Unit Address 2 RS 485 1000 meter Maximum RS 232 10 meter EntryPass Platform1 Access Control System PCC Communicator Rx Tx Power RS232 Serial connection RS485 only applicable for maximum 16 sets S3150 S3200 S3400 The serial address format in Platform1 is 255 255 255 X where X is unit address Connecting to the PC via RS485 Mode ...

Page 24: ...Address 1 RS 232 10 meter EntryPass Platform1 Access Control System 1 2 3 4 5 6 7 8 9 JP4 Serial Port DB9 Female Connector JP4 Serial connection RS232 only applicable for a single S3150 S3200 S3400 The serial address format in Platform1 is 255 255 255 1 Connecting to the PC via RS232 Mode ...

Page 25: ...FF OFF ON OFF Address 09 ON OFF OFF ON OFF Address 10 OFF ON OFF ON OFF Address 11 ON ON OFF ON OFF Address 12 OFF OFF ON ON OFF Address 13 ON OFF ON ON OFF Address 14 OFF ON ON ON OFF Address 15 ON ON ON ON OFF Address 16 OFF OFF OFF OFF ON Each switch is represent by an address the sum of the switch address will be the controller address The number in is the address of each individual switch of ...

Page 26: ...N5400 n N5150 N5200 N5400 1 N5150 N5200 N5400 2 EntryPass Platform1 Server Access Control System Network Switch Cat 5e Network connection only applicable for N5150 N5200 and N5400 Factory default IP address for network controller is 192 168 1 100 Connecting to the PC via Network ...

Page 27: ...rypass Corporation ENTRYPASS TECHNICAL WIRING GUIDE 12V GND AC Fail ACC Backup Battery Monitoring BAT BS Switching Mode Power Supply Unit 12V DC 3A Minimum 12V 12V GND ETH ACC BAT BS Connecting to Power Supply Unit ...

Page 28: ... Press and Hold COLD switch 3 Press RESET Switch and Release RESET switch 4 Release COLD switches when a long beeping sound heard JP1 Buzzer Jumper JP2 Cold Start Initial Button COLD Reset Button RESET Advisable to perform cold start for the first time you turn on the power The buzzer will only beep if jumper is placed on JP2 1 2 Performing Cold Start ...

Page 29: ... Switch and Release RESET switch 4 Release COLD switches when a long beeping sound heard JP1 Buzzer Jumper JP2 Cold Start Initial Button COLD Reset Button RESET Factory Default will change the IP Address back to 192 168 1 100 Server IP to 192 168 1 254 and Port to 2020 For the network controller support AES Encryption feature factory default will disable the AES feature Performing Factory Default ...

Page 30: ...et If the controller is connected with AES enabled Platfrom1 Platfrom1 will sync and update AES setting with the controller Steps of performing AES Hard Reset 1 Please ensure that the jumper is inserted on JP1 3 4 2 Press RESET Switch and Release RESET switch JP1 Reset Button RESET Performing AES Hard Reset ...

Page 31: ...LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2 COM2 VR1 GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3 C3 C2 C2 C1 C1 Input 3 4 Input 1 2 IN1 2 3 4 GND IN1 2 3 4 GND NC Analog Device 3600 Ohm The Inputs are configurable to digital default or analog using Platform1 A resistor of 3600 ohm is required when using analog input This system is not support NO Analog device due to the architecture Upper Connector I2D0...

Page 32: ...r Exit Button PCC Electro magnetic Lock Emergency Breakglass Emergency Keyswitch Entry Reader Exit Reader Controller Network Port Network Switch EntryPass Platform1 Access Control System Power Supply Unit ENTRYPASS 12V 12V ETH ACC BAT For Network Controller Only Serial Controller S3150 S3200 S3400 Network Controller N5150 N5200 N5400 Platform1 Profile In and Out Readers Complete Overview In and Ou...

Page 33: ...1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3 C3 C2 C2 C1 C1 Door Sensor 1 Exit Button 1 Door Sensor 2 Exit Button 2 PCC EntryPass Platform1 Access Control System Electro magnetic Lock 2 Electro magnetic Lock 1 Emergency Breakglass 1 Emergency Keyswitch 1 Emergency Breakglass 2 Power Supply Unit Reader 1 Reader 2 Controller Network Port Network Switch ENTRYPASS 12V 12V ETH ACC BAT Emergency Keyswitch 2 For Ne...

Page 34: ... LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4 COM4 VR2 GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND Lower Connector I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2 COM2 VR1 GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3 C3 C2 C2 C1 C1 Power Supply Unit ENTRYPASS 12V 12V ETH ACC BAT Reader 1 Reader 2 Reader 3 Reader 4 Door Sensor 1 Exit Button 1 Door Sensor 2 Exit Button 2 Electro magnetic Lock 2 Electro mag...

Page 35: ... GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND Lower Connector I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2 COM2 VR1 GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3 C3 C2 C2 C1 C1 Power Supply Unit ENTRYPASS 12V 12V ETH ACC BAT Reader 1 Reader 2 Reader 3 Reader 4 Door Sensor 1 Exit Button 1 Door Sensor 2 Exit Button 2 Door Sensor 3 Exit Button 3 Door Sensor 4 Exit Button 4 Electro magnetic Lock 2 Electro...

Page 36: ... Entry Loop Detector Exit Barrier Entry Loop Detector Entry Reader Exit Reader PCC Exit Barrier Entry Barrier Controller Network Port Network Switch EntryPass Platform1 Access Control System Power Supply Unit ENTRYPASS 12V 12V ETH ACC BAT For Network Controller Only Serial Controller S3150 S3200 S3400 Network Controller N5150 N5200 N5400 Platform1 Profile In and Out Barriers Complete Overview In a...

Page 37: ... NO1 NC2 NO2 COM2 VR1 GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3 C3 C2 C2 C1 C1 Power Supply Unit ENTRYPASS 12V 12V ETH ACC BAT Entry Reader 1 Exit Reader 1 Entry Reader 2 Exit Reader 2 Entry Barrier 1 Exit Barrier 1 Entry Barrier 2 Exit Barrier 2 Entry Barrier Entry Loop Detector 2 Exit Barrier Entry Loop Detector 2 Entry Barrier Entry Loop Detector 1 Exit Barrier Entry Loop Detector 1 For Network Co...

Page 38: ...IN4 GND C3 C3 C2 C2 C1 C1 Entry Reader PCC Bidirectional Turnstile EntryPass Platform1 Access Control System Controller Network Port Network Switch Power Supply Unit ENTRYPASS 12V 12V ETH ACC BAT IN OUT For Network Controller Only Serial Controller S3150 S3200 S3400 Network Controller N5150 N5200 N5400 Platform1 Profile In and Out Turnstile Complete Overview In and Out Turnstile Mode ...

Page 39: ... Mode Exit Reader Rx Tx Power RS232 I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2 COM2 VR1 GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3 C3 C2 C2 C1 C1 Entry Reader PCC EntryPass Platform1 Access Control System Controller Network Port Network Switch For Network Controller Only Power Supply Unit ENTRYPASS 12V 12V ETH ACC BAT IN OUT Complete Overview 2 Turnstiles Mode ...

Page 40: ...7 IN8 IN9 GND Lower Connector I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2 COM2 VR1 GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3 C3 C2 C2 C1 C1 Power Supply Unit ENTRYPASS 12V 12V ETH ACC BAT Entry Reader 1 Exit Reader 1 Entry Reader 2 Exit Reader 2 Bidirectional Turnstile 1 Bi Directional Turnstile 2 For Network Controller Only Serial Controller S3400 Network Controller N5400 Platform1 Profile ...

Page 41: ... GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND Lower Connector I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2 COM2 VR1 GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3 C3 C2 C2 C1 C1 Power Supply Unit ENTRYPASS 12V 12V ETH ACC BAT Reader 1 Reader 2 Reader 3 Reader 4 Turnstile 1 Turnstile 2 Turnstile 3 Turnstile 4 For Network Controller Only Serial Controller S3400 Network Controller N5400 Platform1 Profile ...

Page 42: ...ork Switch Network 100m 300 ft 24 AWG 4 Pairs Cat 5e Controller to Reader Wiegand 30m 100 ft 22 AWG 2 Pairs Shielded Twisted Pair Controller to Electro Magnetic Lock Power 30m 100 ft 18 AWG 1 Pair Controller to Push Button Contact 30m 100 ft 22 AWG 1 Pair Controller to Door Sensor Contact 30m 100 ft 22 AWG 1 Pair Controller to Controller for Cross Board Interlock Contact 100m 300 ft 22 AWG 1 Pair ...