EBER 9000 WITH 1,2 OR 3 REMOVABLE HEAT EXCHANGERS
AND ELECTRIC ELEMENT OPTION
•
Heat Exchanger Efficiencies for DHW Heating from 15°C to 60°C
•
Heat Exchanger Inlet Temperatures 80°C
➢
The Lower Heat Exchanger Heats 88% of the Tank
➢
The Middle Heat Exchanger Heats 61% of the Tank
➢
The Upper Heat Exchanger Heats 37% of the Tank
ABREVIATIONS
CWI
Cold Water Inlet
HWO
Hot Water Outlet
R
Recirculation
VEN
Ventilation
CI
Coil Inlet
CO
Coil Outlet
S
Sensor
T
Thermostat
TR
Thermometer
EH
Electric Heating Element
HEAT EXCHANGER COMBINATIONS AVAILABLE
Lower
Heat
Exchanger
Upper
Heat
Exchanger
Middle
Heat
Exchanger
Total H.E.
Surface
7,8m
2
7,8m
2
7,8m
2
23,4m
2
EFFICIENCY OF ALL 3 HEAT EXCHANGERS
FLOW RATE
7,8m
2
Lower Heat
Exchanger Efficiency
7,8m
2
Middle Heat
Exchanger Efficiency
7,8m
2
Upper Heat
Exchanger Efficiency
3000 Lt/h
104,70Kw
104,30Kw
105,40Kw
4500 Lt/h
125,30Kw
124,60Kw
124,20Kw
6000 Lt/h
138,60Kw
137,60Kw
137,30Kw