3) MAIN BURNERS WILL
NOT LIGHT
Make sure gas valve knob is
in the “ON” position.
SEE PAGE 8 FIGURE 6.
Correct if necessary.
Turn valve to the “ON”
position.
Make sure that the “ON-OFF
THERMO” switch is in the
“ON” position.
Turn switch “ON”.
Make sure that the
thermostat is “NOT” in the
lowest position.
Turn thermostat “UP”.
Replace damaged wires as
necessary. Gently squeeze
connectors with a pair of
pliers and reinstall wires.
Make sure that all control
wires are not damaged,
broken or frayed and that all
wire connections are tight.
Tighten the two screws on
valve if necessary
“TP/TP-TH” terminals on
valve.
Make sure that the
thermopile connections are
tight on the valve.
Make sure millivolt readings
from thermopile are within
manufactures
specifications. MAKE SURE
MILLIVOLT READINGS ARE
CONSTANT.
SEE PAGE 6 FIGURE 8.
Place leads of multimeter
on the “TP/TH-TP”
terminals on gas valve. If
the readings are less than
145mV DC, replace
thermopile
Continued on next page.
Sherwood Industries Ltd.
ENVIRO
PAGE 9