MAIN BURNERS WILL NOT LIGHT CON’T.
Bypass spill switch with a
jumper wire as shown. If the
unit starts, replace the spill
switch. DO NOT LEAVE BY
PASSED IN.
Check spill switch operation
on B-vented models only
SEE PAGE 10 FIGURE 9.
Check the “ON-OFF” switch
and thermostat for proper
operation.
Use a jumper wire. If the unit
starts, replace switch if
necessary.
Make sure that the main
burner orifices are not
clogged or damaged.
Remove the top tray.
Remove orifice and clean.
Replace if damaged.
Sherwood Industries Ltd.
ENVIRO
PAGE 10