5) SOOTING
Make sure log placement is
in the correct location.
Correct to manufactures
specifications.
Correct if necessary.
Outside air supply may be
required on B-vented
models.
Make sure there is sufficient
air supply.
Check air shutter on the
venturi tube for proper
primary air adjustment.
SEE PAGE 16.
Increase primary air.
Open air shutter.
Make sure orifice matches
that on the rating plate.
Correct if necessary.
Make sure outlet (manifold)
pressure is correct.
Use a manometer to check
the gas pressure.
SEE PAGE 5 FIGURE 7.
Make sure the unit has been
derated for high altitude
applications.
(if required)
Correct if necessary.
Check to make sure that the
vent is drafting properly.
Correct if necessary.
Sherwood Industries Ltd.
ENVIRO
PAGE 15
Summary of Contents for C-10100
Page 4: ...3 175mm Sherwood Industries Ltd ENVIRO PAGE 2 ...
Page 10: ...S I T EUROSIT MODULATING 630 SERIES Sherwood Industries Ltd ENVIRO PAGE 8 ...
Page 14: ...Sherwood Industries Ltd ENVIRO PAGE 12 ...
Page 15: ...SAMPLE DIRECT VENT CHIMNEY INSTALLATIONS ALL MODELS Sherwood Industries Ltd ENVIRO PAGE 13 ...