2) PILOT WILL NOT STAY
LIT
Use a manometer on the inlet
side of the valve to measure
gas pressure. Adjust inlet
pressure or contact your gas
supplier.
Make sure the gas pressure is
correct for type of fuel you are
using.
SEE PAGE 5 FIGURE 7.
Thermocouple should be the
same height as the pilot hood.
Make sure pilot flame is
engulfing the top 3/8” of the
thermocouple.
SEE PAGE 2 FIGURE 2.
Adjust pilot as required.
Check for clogged pilot
injector.
Make sure thermocouple
connections on valve are
tight.
DO NOT OVER TIGHTEN!!!
Thermocouple connections
should be hand tight plu1/4
turn.
Clean thermocouple ends
with Emery cloth or an
abrasive sponge.
DO NOT USE A METAL FILE.
Replace if damaged.
Make sure the thermocouple
line has no kinks and is clean
on both ends. Also check the
thermocouple for damage.
Using a multimeter, insert
adapter between valve and
thermocouple, if the readings
are less than 2 TO 6 mV DC,
replace thermocouple.
SEE PAGE 6 FIGURE 8.
Make sure the thermocouple
has proper voltage (DC
VOLTAGE).