H
OT
W
ATER
C
OIL
D
ATA
• CFR
©December, 2005 Environmental Technologies, Inc.
• CFR Catalog
25
NOTES:
1. Data is based on 180°F entering water and 65°F entering air temperature at sea level. See selection procedure for other conditions.
2. For optimum diffuser performance in overhead heating applications, the supply air temperature should be within 20°F of the desired
space temperature. This typically requires a higher air capacity which provides higher air motion in the space, increasing thermal com-
fort. The hot water coil should be selected with this in mind, keeping the LAT as low as possible.
The ENVIRO-TEC
®
Windows
®
based Computer Selection Program is available through your ENVIRO-TEC
®
representative for com-
plete CFR selection and hot water coil performance data.
1 Row
2 Row
1 Row
2 Row
1 Row
2 Row
1 Row
2 Row
0.5
0.4
0.1
107.4
124.1
142.5
127.8
9.2
12.8
1
1.2
0.4
114.1
136.1
158.2
148.5
10.6
15.4
2
4.4
1.2
118.4
143.5
168.1
162.5
11.6
17.0
3
9.2
2.6
120.0
146.3
171.8
167.9
11.9
17.6
4
15.5
4.4
120.9
147.7
173.8
170.8
12.1
17.9
5
-
6.6
-
148.6
-
172.6
-
18.1
0.5
0.4
0.1
98.5
111.3
135.5
118.7
10.9
15.1
1
1.2
0.4
105.3
124.0
153.2
140.8
13.1
19.2
2
4.4
1.2
109.7
132.6
165.1
157.5
14.5
22.0
3
9.2
2.6
111.5
136.0
169.6
164.2
15.1
23.1
4
15.5
4.4
112.5
137.8
172.1
167.8
15.4
23.7
5
-
6.6
-
139.0
-
170.1
-
24.0
0.5
0.4
0.1
93.0
103.2
130.5
112.7
12.1
16.5
1
1.2
0.4
99.5
115.6
149.4
135.2
14.9
21.9
2
4.4
1.2
104.0
124.8
162.7
153.5
16.9
25.9
3
9.2
2.6
105.8
128.5
167.9
161.2
17.7
27.5
4
15.5
4.4
106.8
130.5
170.7
165.4
18.1
28.4
5
-
6.6
-
131.8
-
168.1
-
28.9
0.5
0.4
0.1
89.1
97.5
126.7
108.5
13.1
17.6
1
1.2
0.4
95.4
109.4
146.4
130.9
16.4
24.0
2
4.4
1.2
99.8
118.7
160.6
150.2
18.9
29.1
3
9.2
2.6
101.7
122.6
166.4
158.7
19.9
31.2
4
15.5
4.4
102.7
124.8
169.5
163.4
20.4
32.4
5
-
6.6
-
126.2
-
166.4
-
33.1
0.5
0.4
0.1
86.2
93.3
123.7
105.3
13.8
18.4
1
1.2
0.4
92.2
104.6
143.8
127.5
17.7
25.7
2
4.4
1.2
96.6
113.9
158.9
147.5
20.6
31.8
3
9.2
2.6
98.5
117.9
165.1
156.5
21.7
34.4
4
15.5
4.4
99.5
120.2
168.5
161.6
22.4
35.9
5
-
6.6
-
121.6
-
164.9
-
36.8
0.5
0.4
0.1
84.0
90.1
121.2
102.8
14.4
19.0
1
1.2
0.4
89.7
100.8
141.7
124.7
18.7
27.1
2
4.4
1.2
94.0
110.0
157.4
145.1
22.0
34.1
3
9.2
2.6
95.9
114.1
164.0
154.6
23.4
37.2
4
15.5
4.4
96.9
116.4
167.6
160.0
24.2
38.9
5
-
6.6
-
117.9
-
163.5
-
40.1
0.5
0.4
0.1
82.2
87.5
119.1
100.8
14.9
19.5
1
1.2
0.4
87.7
97.7
139.8
122.3
19.7
28.3
2
4.4
1.2
91.9
106.7
156.1
143.1
23.3
36.1
3
9.2
2.6
93.7
110.8
163.0
152.9
24.9
39.7
4
15.5
4.4
94.7
113.1
166.8
158.6
25.8
41.7
5
-
6.6
-
114.6
-
162.3
-
43.0
0.5
0.4
0.1
80.8
85.4
117.4
99.1
15.4
19.9
1
1.2
0.4
86.0
95.1
138.1
120.3
20.5
29.3
2
4.4
1.2
90.1
103.9
154.9
141.3
24.5
37.9
3
9.2
2.6
91.9
108.0
162.0
151.4
26.2
41.9
4
15.5
4.4
92.9
110.3
166.0
157.4
27.2
44.2
5
-
6.6
-
111.9
-
161.3
-
45.7
0.5
0.4
0.1
79.6
83.7
115.8
97.7
15.8
20.3
1
1.2
0.4
84.6
92.9
136.7
118.5
21.2
30.2
2
4.4
1.2
88.6
101.5
153.8
139.6
25.6
39.5
3
9.2
2.6
90.4
105.5
161.2
150.0
27.5
43.9
4
15.5
4.4
91.4
107.9
165.3
156.2
28.6
46.5
5
-
6.6
-
109.4
-
160.3
-
48.1
0.5
0.4
0.1
78.5
82.3
114.4
96.5
16.1
20.6
1
1.2
0.4
83.3
91.0
135.4
116.9
21.9
31.0
2
4.4
1.2
87.3
99.4
152.8
138.2
26.6
40.9
3
9.2
2.6
89.0
103.4
160.4
148.8
28.6
45.7
4
15.5
4.4
90.0
105.7
164.7
155.1
29.8
48.5
5
-
6.6
-
107.3
-
159.3
-
50.4
700
1 Row 0.08
2 Row 0.15
800
1 Row 0.10
2 Row 0.19
Water PD
(FT. W.G.)
600
1 Row 0.06
2 Row 0.12
400
1 Row 0.03
2 Row 0.06
500
1 Row 0.04
2 Row 0.08
300
1 Row 0.02
2 Row 0.03
CAPACITY
(MBH)
LWT (°F)
LAT (°F)
1 Row 0.01
2 Row 0.02
AIRFLOW
WATER FLOW
200
Rate
(CFM)
Air PD
(IN. W.G.)
Rate
(GPM)
1100
1 Row 0.17
2 Row 0.34
900
1 Row 0.12
2 Row 0.24
1000
1 Row 0.14
2 Row 0.29
M
ODEL
CFR-WC
• U
NIT
S
IZES
0606, 0806, 0611, 0811, 1011