CFR •
C
ONSTRUCTION
F
EATURES
4
CFR Catalog • ©
May, 2006 Environmental Technologies, Inc.
Model CFR
The CFR terminal incorporates many unique features. Most of these
standard
features are expensive options for other manufacturers.
Integral discharge collar
simplifies field installation
All unit configurations
listed with ETL for
safety compliance
Product label includes
tagging, airflow, and
electrical information
Mechanical lock construction
ensures lowest possible
casing leakage
Full bottom removable
access panels
Low leakage damper incorporates
closed cell foam gasket
Roll formed inlet collar with integral
stiffening ribs adds strength and rigidity
Patented FlowStar
TM
airflow sensor
(Patent #5,481,925)
Galvanized steel casing withstands 125
hour salt spray test per ASTM B-117
Mechanically fastened
insulation for added
security
3/4" thick, 4lb/ft
3
skin,
dual density insulation
complying with UL 181
and NFPA 90A
Fan assembly utilizes a forward curved,
dynamically balanced, galvanized wheel
with a direct drive motor
Electrical devices
installed within a
NEMA 1enclosure,
with single point
power connection
Optional Construction Features
• ECM™ fan motor
• Mounting brackets to accept all-thread hanging rods or wire hangers
• Double wall construction
• Scrim reinforced foil faced insulation meeting ASTM C1136 for mold, mildew, and humidity resistance
• Filter located at induction inlet
• Hot water (CFR-WC), steam, or electric heating coils (CFR-EH) mounted at unit discharge. Access plate upstream
of hydronic coil is standard.
• Low temperature construction for use in thermal storage applications. Includes thermally isolated primary air
inlet and composite damper shaft.
• Factory control options: analog electronic, DDC electronic, pneumatic
• Factory piping packages (refer to Piping Packages catalog, Stock ID CAT-PIPING)
• Induction inlet gravity damper reduces radiated NC level by up to 2 NC at full cooling condition.