ENVIRO-TEC
28
FORM ET115.24-NOM4 (819)
SECTION 2 - START-UP
Refer to
Figure 12 on page 25
for location of Con-
figuration Switch, speed Adjust Potentiometer, and
Reset Button. These will be used to program the EC
operating mode and motor speed settings.
Three Speed (Adjustable) Motor Control
High, Medium, and/or Low speed adjustment for three
speed operation.
Thermostat must be set for three speed
operation.
1.
High Speed Setting Adjust:
Set Configuration
Switch to HIGH SPEED adjust (see
Figure 16 on
page 28
). Switches to ON-OFF-ON-OFF-OFF-
OFF-OFF-OFF.
• Set switch 1 to ON (Program).
• Set switch 2 to OFF (Fixed Speed).
• Set switch 3 to ON (Hi/Max).
• Set switches 4 through 8 to OFF.
• Press RESET button.
RESET button only needs to be pressed
once per programming session unless
board times out. Refer to Status LED.
• Refer to voltmeter connected to TP1 and
TP3. Using an insulated 1/8” flat bladed
screwdriver, adjust speed potentiometer to
desired high speed airflow per Fan Calibra-
tion Curve on unit.
•
STORE:
Set switch 8 to Store (ON), wait
one second, then to Set (OFF), to save the
value.
FIGURE 16 -
HIGH SPEED ADJUST
2.
Medium speed Adjust:
Set Configuration Switch
to MEDIUM SPEED adjust (see
Figure 17 on
page 28
). Switches to ON-OFF-OFF-ON-OFF-
OFF-OFF-OFF.
• Set switch 1 to ON (Program).
• Set switches 2 -3 to OFF.
• Set switch 4 to ON (Med).
• Set switches 5 through 8 to OFF.
• Refer to voltmeter connected to TP1 and
TP3. Using an insulated 1/8” flat bladed
screwdriver, adjust speed potentiometer to
desired high speed airflow per Fan Calibra-
tion Curve on unit.
•
STORE:
Set switch 8 to Store (ON), wait
one second, then to Set (OFF), to save the
value.
FIGURE 17 -
MEDIUM SPEED ADJUST
Summary of Contents for VHA
Page 10: ...ENVIRO TEC 10 FORM ET115 24 NOM4 819 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 41: ...ENVIRO TEC 41 SECTION 2 START UP FORM ET115 24 NOM4 819 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 54: ...ENVIRO TEC 54 FORM ET115 24 NOM4 819 SECTION 6 Dimensional Data 74 80083 ...